recordReformEIRChiller_York_YT_3133kW_9_16COP_Vanes

ReformEIRChiller York YT 3133kW/9.16COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 3133kW/9.16COP/Vanes,  !- Name
    3133300,                 !- Reference Capacity {W}
    9.16,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    19.37,                   !- Reference Leaving Condenser Water Temperature {C}
    0.08076,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.12618,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 3133kW/9.16COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 3133kW/9.16COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 3133kW/9.16COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.07,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.07,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-3133300
COP_nominal9.16
PLRMin0.07
PLRMinUnl0.07
PLRMax1.04
mEva_flow_nominal1000*0.08076
mCon_flow_nominal1000*0.12618
TEvaLvg_nominal273.15 + 5.56
TConLvg_nominal273.15 + 19.37
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 19.37
TConLvgMax273.15 + 35.91
capFunT{6.112157E-01, -1.430728E-02, 9.823748E-05, 3.293543E-02, -1.221859E-03, 2.659301E-03}
EIRFunT{8.749714E-01, -2.881975E-02, 2.003695E-03, 7.313755E-03, 5.578288E-04, -1.170615E-03}
EIRFunPLR{3.389568E-01, -1.864923E-02, 3.548361E-04, 1.107404E+00, -5.912797E-01, -4.559304E-04, 0.000000E+00, 3.910858E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0