recordReformEIRChiller_York_YT_960kW_4_64COP_Vanes

ReformEIRChiller York YT 960kW/4.64COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 960kW/4.64COP/Vanes,  !- Name
    960000,                  !- Reference Capacity {W}
    4.64,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    32.01,                   !- Reference Leaving Condenser Water Temperature {C}
    0.03785,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 960kW/4.64COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 960kW/4.64COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 960kW/4.64COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.1,                     !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-960000
COP_nominal4.64
PLRMin0.09
PLRMinUnl0.09
PLRMax1.1
mEva_flow_nominal1000*0.03785
mCon_flow_nominal1000*0.04732
TEvaLvg_nominal273.15 + 4.44
TConLvg_nominal273.15 + 32.01
TEvaLvgMin273.15 + 3.33
TEvaLvgMax273.15 + 7.78
TConLvgMin273.15 + 17.04
TConLvgMax273.15 + 35.78
capFunT{-3.474613E-01, 4.071500E-01, -3.270717E-02, 1.187286E-02, -3.117876E-04, 5.854731E-04}
EIRFunT{6.522319E-01, -1.649356E-02, 2.777675E-04, 3.580800E-03, 3.253181E-04, -2.452307E-04}
EIRFunPLR{3.303041E-01, -1.499923E-03, 4.911711E-06, 3.166646E-01, 4.011833E-01, 1.242191E-03, 0.000000E+00, -4.559734E-02, 0.000000E+00, 0.000000E+00}
etaMotor1.0