modelCarnot_TEva_HighTemperature

Test model for Carnot_TEva with high evaporator temperature

Extends from Examples.Carnot_TEva (Test model for chiller based on Carnot efficiency and evaporator outlet temperature control signal).

Information

This example extends from Buildings.Fluid.Chillers.Examples.Carnot_TEva but increases the set point for the leaving evaporator temperature to be above its inlet temperature, in which case the model provides no cooling. Towards the end of the simulation, the inlet temperature of the evaporator is increased to be above the condenser temperature. In this domain, the model requires cooling again. While this is not a meaningful operating point for the model, the example verifies that it robustly simulates this regime.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.TemperatureDifferencedTEva_nominal (from Carnot_TEva)-10Temperature difference evaporator outlet-inlet
Modelica.Units.SI.TemperatureDifferencedTCon_nominal (from Carnot_TEva)10Temperature difference condenser outlet-inlet
RealCOPc_nominal (from Carnot_TEva)3Chiller COP
Modelica.Units.SI.HeatFlowRateQEva_flow_nominal (from Carnot_TEva)-100E3Evaporator heat flow rate
Modelica.Units.SI.MassFlowRatem2_flow_nominal (from Carnot_TEva)QEva_flow_nominal/dTEva_nominal/4200Nominal mass flow rate at chilled water side
Modelica.Units.SI.SpecificHeatCapacitycp1_default (from Carnot_TEva)Medium1.specificHeatCapacityCp(Medium1.setState_pTX(Medium1.p_default, Medium1.T_default, Medium1.X_default))Specific heat capacity of medium 1 at default medium state

Components

TypeNameDefaultDescription
Buildings.Fluid.Chillers.Carnot_TEvachi (from Carnot_TEva)Chiller model
Buildings.Fluid.Sources.MassFlowSource_Tsou1 (from Carnot_TEva)
Buildings.Fluid.Sources.MassFlowSource_Tsou2 (from Carnot_TEva)
Buildings.Fluid.Sources.Boundary_pTsin1 (from Carnot_TEva)
Buildings.Fluid.Sources.Boundary_pTsin2 (from Carnot_TEva)
Modelica.Blocks.Sources.RampTEvaLvg (from Carnot_TEva)Control signal for evaporator leaving temperature
Modelica.Blocks.Math.GainmCon_flow (from Carnot_TEva)Condenser mass flow rate
Modelica.Blocks.Math.AddQCon_flow (from Carnot_TEva)Condenser heat flow rate
Modelica.Blocks.Sources.RampTEvaEntControl signal for evaporator entering temperature

Revisions

  • February 10, 2016, by Michael Wetter:
    First implementation.