modelCarnot_y_etaPL
Test model for the part load efficiency curve with compressor speed as input signal
Extends from Examples.Carnot_y (Test model for chiller based on Carnot_y efficiency).
Information
This example extends from Buildings.Fluid.Chillers.Examples.Carnot_y but uses a part load efficiency curve that is different from 1.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Power | P_nominal (from Carnot_y) | 10E3 | Nominal compressor power (at y=1) |
| Modelica.Units.SI.TemperatureDifference | dTEva_nominal (from Carnot_y) | -10 | Temperature difference evaporator outlet-inlet |
| Modelica.Units.SI.TemperatureDifference | dTCon_nominal (from Carnot_y) | 10 | Temperature difference condenser outlet-inlet |
| Real | COPc_nominal (from Carnot_y) | 3 | Chiller COP |
| Modelica.Units.SI.MassFlowRate | m2_flow_nominal (from Carnot_y) | -P_nominal*COPc_nominal/dTEva_nominal/4200 | Nominal mass flow rate at chilled water side |
| Modelica.Units.SI.MassFlowRate | m1_flow_nominal (from Carnot_y) | m2_flow_nominal*(COPc_nominal + 1)/COPc_nominal | Nominal mass flow rate at condenser water wide |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Fluid.Chillers.Carnot_y | chi (from Carnot_y) | Chiller model | |
| Buildings.Fluid.Sources.MassFlowSource_T | sou1 (from Carnot_y) | ||
| Buildings.Fluid.Sources.MassFlowSource_T | sou2 (from Carnot_y) | ||
| Buildings.Fluid.Sources.Boundary_pT | sin1 (from Carnot_y) | ||
| Buildings.Fluid.Sources.Boundary_pT | sin2 (from Carnot_y) | ||
| Modelica.Blocks.Sources.Ramp | uCom (from Carnot_y) | Compressor control signal | |
| Modelica.Blocks.Sources.Ramp | TCon_in (from Carnot_y) | Condenser inlet temperature | |
| Modelica.Blocks.Sources.Ramp | TEva_in (from Carnot_y) | Evaporator inlet temperature |
Revisions
-
February 10, 2016, by Michael Wetter:
First implementation.