recordNominalValues

Data record of nominal values

Extends from Modelica.Icons.Record (Icon for records).

Information

This is the base record of nominal values for air source DX cooling coil models.

See the information section of Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.DXCoil for a description of the data.

Parameters

TypeNameDefaultDescription
Nominal condition
Modelica.Units.SI.HeatFlowRateQ_flow_nominalNominal capacity (negative number)
RealCOP_nominalNominal coefficient of performance
RealSHR_nominalNominal sensible heat ratio
Modelica.Units.SI.MassFlowRatem_flow_nominalNominal air mass flow rate at evaporators
General › Nominal condition
Modelica.Units.SI.TemperatureTEvaIn_nominal292.55Evaporator entering air wet-bulb temperature at rating condition
Modelica.Units.SI.TemperatureTConIn_nominal308.15Condenser entering temperature at rating condition (wet bulb for evaporative cooled coils, dry bulb for air cooled)
Modelica.Units.SI.Pressurep_nominal101325Atmospheric pressure
General › Nominal
RealphiIn_nominal0.5Relative humidity of entering air at nominal condition
General › Re-evaporation data
Modelica.Units.SI.TimetWet1400Time until moisture drips from coil when a dry coil is switched on
Realgamma1.5Ratio of evaporation heat transfer divided by latent heat transfer at nominal conditions

Revisions

  • March 19, 2023 by Xing Lu and Karthik Devaprasad:
    Added Boolean conditional for cooling mode operation. Added conditional enable to parameters for SHR_nominal, tWet and gamma.
  • September 25, 2012 by Michael Wetter:
    Revised documentation.
  • September 4, 2012 by Michael Wetter:
    Added parameters for evaporation model.
  • August 13, 2012 by Kaustubh Phalak:
    First implementation.