recordGeneric

Performance data record for a wet cooling tower that uses Merkel's model

Extends from Buildings.Fluid.HeatExchangers.CoolingTowers.Data.BaseClasses.BaseCoolingTower (Performance data record for dry and wet cooling towers).

Information

Performance data record for a wet cooling tower that uses Merkel's method.

Parameters

TypeNameDefaultDescription
RealPFan_Q_flow_nominal (from BaseCoolingTower)-0.05Ratio of fan power to provided cooling at full load (negative as Q_flow_nominal<0)
Modelica.Units.SI.PowerPFan_nominal (from BaseCoolingTower)abs(PFan_Q_flow_nominal*Q_flow_nominal)Fan power at full speed
Nominal thermal performance
Modelica.Units.SI.HeatFlowRateQ_flow_nominal (from BaseCoolingTower)Nominal heat flow rate (negative, as heat is removed from the fluid)
Modelica.Units.SI.TemperatureTCooIn_nominal (from BaseCoolingTower)Nominal cooling loop inlet temperature
Modelica.Units.SI.TemperatureTCooOut_nominal (from BaseCoolingTower)Nominal cooling loop outlet temperature
Modelica.Units.SI.TemperatureTAirInWB_nominal298.7Nominal outdoor (air inlet) wetbulb temperature
Nominal condition
Modelica.Units.SI.PressureDifferencedp_nominal (from BaseCoolingTower)Pressure difference at design mass flow rate
Advanced
RealratCooAir_nominal (from BaseCoolingTower)Coolant-to-air mass flow rate ratio at design condition, used to compute air flow rate for UA_value
Buildings.Fluid.HeatExchangers.CoolingTowers.BaseClasses.Characteristics.fanfanRelPow (from BaseCoolingTower)Fan relative power consumption as a function of control signal, fanRelPow=P(y)/P(y=1)
RealfraFreCon (from BaseCoolingTower)0.125Fraction of tower capacity in free convection regime
BaseClasses.UACorrectionUACorUA correction factors

Revisions

  • April 22, 2026, by Michael Wetter:
    First implementation.