modelEffectivenessNTUMassFlow

Partial model of epsilon-NTU coil that tests variable mass flow rates

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.TemperatureT_a1_nominal5 + 273.15Nominal water inlet temperature
Modelica.Units.SI.TemperatureT_b1_nominal10 + 273.15Nominal water outlet temperature
Modelica.Units.SI.TemperatureT_a2_nominal30 + 273.15Nominal air inlet temperature
Modelica.Units.SI.TemperatureT_b2_nominal15 + 273.15Nominal air outlet temperature
Modelica.Units.SI.HeatFlowRateQ_flow_nominalm1_flow_nominal*4200*(T_a1_nominal - T_b1_nominal)Nominal heat transfer
Modelica.Units.SI.MassFlowRatem1_flow_nominal0.1Nominal mass flow rate medium 1
Modelica.Units.SI.MassFlowRatem2_flow_nominalm1_flow_nominal*4200/1000*(T_a1_nominal - T_b1_nominal)/(T_b2_nominal - T_a2_nominal)Nominal mass flow rate medium 2

Components

TypeNameDefaultDescription
Buildings.Fluid.Sources.MassFlowSource_Tsin_2Sink for air
Buildings.Fluid.Sources.Boundary_pTsou_2Source for air
Buildings.Fluid.Sources.MassFlowSource_Tsin_1Sink for water
Buildings.Fluid.Sources.Boundary_pTsou_1Source for water
Modelica.Blocks.Sources.ConstantrelHumRelative humidity
Buildings.Utilities.Psychrometrics.X_pTphix_pTphi
Modelica.Blocks.Sources.ConstanttemSou_2Temperature boundary condition
Modelica.Blocks.Math.GainmWat_flowWater mass flow rate
Modelica.Blocks.Sources.TimeTablemWatGaiGain for water mass flow rate
Modelica.Blocks.Sources.TimeTablemAirGaiGain for air mass flow rate
Modelica.Blocks.Math.GainmAir_flowAir mass flow rate

Contents

NameDescription
Medium1Medium model for water
Medium2Medium model for air