modelWetCoilCounterFlowPControl
Model that demonstrates use of a heat exchanger with condensation and with feedback control
Extends from Modelica.Icons.Example (Icon for runnable examples), Buildings.Fluid.HeatExchangers.Examples.BaseClasses.PartialWetCoilCounterFlow (Partial model that demonstrates use of a heat exchanger with condensation and with feedback control).
Information
This model demonstrates the use of Buildings.Fluid.HeatExchangers.WetCoilCounterFlow. The valve on the water-side is regulated to track a setpoint temperature for the air outlet.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Temperature | T_a1_nominal (from PartialWetCoilCounterFlow) | 5 + 273.15 | |
| Modelica.Units.SI.Temperature | T_b1_nominal (from PartialWetCoilCounterFlow) | 10 + 273.15 | |
| Modelica.Units.SI.Temperature | T_a2_nominal (from PartialWetCoilCounterFlow) | 30 + 273.15 | |
| Modelica.Units.SI.Temperature | T_b2_nominal (from PartialWetCoilCounterFlow) | 15 + 273.15 | |
| Modelica.Units.SI.MassFlowRate | m1_flow_nominal (from PartialWetCoilCounterFlow) | 0.1 | Nominal mass flow rate medium 1 |
| Modelica.Units.SI.MassFlowRate | m2_flow_nominal (from PartialWetCoilCounterFlow) | 0.2*m1_flow_nominal*4200/1000*(T_a1_nominal - T_b1_nominal)/(T_b2_nominal - T_a2_nominal) | Nominal mass flow rate medium 2 |
Components
Revisions
-
December 14, 2023 by Jianjun Hu:
Reduced the nominal airflow rate and the water temperature. This is for #3607. -
December 22, 2014 by Michael Wetter:
RemovedModelica.Fluid.Systemto address issue #311. -
March 1, 2013, by Michael Wetter:
Added nominal pressure drop for valve as this parameter no longer has a default value. -
May 27, 2010, by Michael Wetter:
First implementation.