modelPartialModularComparison

Partial model for comparison to the Carnot model

Extends from PartialComparison (Partial model to allow heat pump and chiller model comparison).

Information

Partial model to have consitent parameterization of the modular reversible model approaches.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.HeatFlowRateQUse_flow_nominal (from PartialComparison)30E3Nominal capacity
Modelica.Units.SI.TemperatureDifferencedTEva_nominal (from PartialComparison)10Temperature difference evaporator outlet-inlet
Modelica.Units.SI.TemperatureDifferencedTCon_nominal (from PartialComparison)10Temperature difference condenser outlet-inlet
Modelica.Units.SI.Pressuredp1_nominal (from PartialComparison)6000Pressure difference over condenser
Modelica.Units.SI.Pressuredp2_nominal (from PartialComparison)6000Pressure difference over evaporator
RealetaCarnot_nominal (from PartialComparison)0.3Carnot effectiveness (=COP/COP_Carnot) used during simulation if use_eta_Carnot_nominal = true
Modelica.Units.SI.Timetau1 (from PartialComparison)60Time constant at nominal flow rate (used if energyDynamics1 <> Modelica.Fluid.Types.Dynamics.SteadyState)
Modelica.Units.SI.TemperatureT1_start (from PartialComparison)303.15Initial or guess value of set point
Modelica.Units.SI.Timetau2 (from PartialComparison)60Time constant at nominal flow rate (used if energyDynamics2 <> Modelica.Fluid.Types.Dynamics.SteadyState)
Modelica.Units.SI.TemperatureT2_start (from PartialComparison)278.15Initial or guess value of set point
Modelica.Units.SI.TemperatureTConIn_nominal (from PartialComparison)303.15Nominal condenser inlet temperature
Modelica.Units.SI.TemperatureTEvaIn_nominal (from PartialComparison)288.15Nominal condenser inlet temperature
Modelica.Units.SI.TemperatureTCon_nominal (from PartialComparison)TConIn_nominal + dTCon_nominalNominal condenser temperature
Modelica.Units.SI.TemperatureTEva_nominal (from PartialComparison)TEvaIn_nominal - dTEva_nominalNominal evaporator temperature
Modelica.Units.SI.MassFlowRatem2_flow_nominal (from PartialComparison)Nominal mass flow rate at chilled water side
Modelica.Units.SI.MassFlowRatem1_flow_nominal (from PartialComparison)Nominal mass flow rate at condenser water wide

Components

TypeNameDefaultDescription
Buildings.Fluid.Sources.MassFlowSource_Tsou1 (from PartialComparison)Condenser mass flow source
Buildings.Fluid.Sources.MassFlowSource_Tsou2 (from PartialComparison)Evaporator mass flow source
Buildings.Fluid.Sources.Boundary_pTsin1 (from PartialComparison)
Buildings.Fluid.Sources.Boundary_pTsin2 (from PartialComparison)
Modelica.Blocks.Sources.RampuCom (from PartialComparison)Compressor control signal
Modelica.Blocks.Sources.RampTCon_in (from PartialComparison)Condenser inlet temperature
Modelica.Blocks.Sources.RampTEva_in (from PartialComparison)Evaporator inlet temperature
Buildings.Fluid.HeatPumps.ModularReversible.ModularheaPumModular heat pump model

Revisions

  • November 13, 2023 by Fabian Wuellhorst:
    First implementation.