modelDiversion
Diversion circuit
Extends from Fluid.HydronicConfigurations.Interfaces.PartialHydronicConfiguration.
Information
Summary
This configuration (see schematic below) is used for constant flow primary circuits and variable flow consumer circuits where the consumer circuit has the same supply temperature set point as the primary circuit.
The following table presents the main characteristics of this configuration.
| Primary circuit | Constant flow |
| Secondary (consumer) circuit | Variable flow |
| Typical applications | Single heating or cooling coil served by a constant flow circuit |
| Non-recommended applications |
DHC systems due to the significant recirculating primary flow rate at low load Heating systems with condensing boilers for the same reason |
| Built-in valve control options | No built-in controls |
| Control valve selection |
β = ΔpA-AB /
(Δp2 + ΔpA-AB) =
ΔpA-AB /
(Δp1 - ΔpAB-b1) The valve is sized with a pressure drop of Δp2 for a mass flow rate equal to the consumer circuit design flow. |
| Balancing requirement | The bypass balancing valve is not needed in most cases. If the valve has a low authority and the consumer circuit has a high pressure drop (compared to the primary pump head) then a bypass balancing valve should be used and sized so that ΔpJ-B + ΔpB-AB = Δp2 + ΔpA-AB for a mass flow rate equal to the consumer circuit design flow. |
|
Lumped flow resistances include (With the setting use_lumFloRes=true.)
|
Direct branch: control valve direct branch val.res1
and whole consumer circuit between b2 and a2Bypass branch: control valve bypass branch val.res3
and bypass balancing valve res3
|
Additional comments
See the example Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Examples.DiversionOpenLoop for additional comments regarding the need for a balanced bypass.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | n (from PartialHydronicConfiguration) | 2 | Flow exponent, n1=1 for laminar, n1=2 for turbulent |
| Movers.Data.Generic | perPum (from PartialHydronicConfiguration) | ||
| Configuration | |||
| Boolean | use_siz (from PartialHydronicConfiguration) | true | Set to true for built-in sizing of control valve and optional pump |
| Boolean | use_dp1 (from PartialHydronicConfiguration) | Set to true to enable dp1_nominal | |
| Boolean | use_dp2 (from PartialHydronicConfiguration) | Set to true to enable dp2_nominal | |
| Buildings.Fluid.HydronicConfigurations.Types.Valve | typVal (from PartialHydronicConfiguration) | Type of control valve | |
| Boolean | have_typVar (from PartialHydronicConfiguration) | true | Set to true to enable the choice of the controlled variable |
| Nominal condition | |||
| Modelica.Units.SI.MassFlowRate | m1_flow_nominal (from PartialHydronicConfiguration) | Mass flow rate in primary circuit at design conditions | |
| Modelica.Units.SI.MassFlowRate | m2_flow_nominal (from PartialHydronicConfiguration) | Mass flow rate in consumer circuit at design conditions | |
| Modelica.Units.SI.PressureDifference | dp1_nominal (from PartialHydronicConfiguration) | Primary circuit pressure differential at design conditions | |
| Modelica.Units.SI.PressureDifference | dp2_nominal (from PartialHydronicConfiguration) | Consumer circuit pressure differential at design conditions | |
| Control valve | |||
| Buildings.Fluid.HydronicConfigurations.Types.ValveCharacteristic | typCha (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.ValveCharacteristic.EqualPercentage | Control valve characteristic |
| Modelica.Units.SI.PressureDifference | dpValve_nominal (from PartialHydronicConfiguration) | Control valve pressure drop at design conditions | |
| Actuators.Valves.Data.Generic | flowCharacteristics (from PartialHydronicConfiguration) | Table with flow characteristics | |
| Actuators.Valves.Data.Generic | flowCharacteristics1 (from PartialHydronicConfiguration) | Table with flow characteristics for direct flow path at port_1 | |
| Actuators.Valves.Data.Generic | flowCharacteristics3 (from PartialHydronicConfiguration) | Table with flow characteristics for bypass flow path at port_3 | |
| Pump | |||
| Buildings.Fluid.HydronicConfigurations.Types.Pump | typPum (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.Pump.VariableInput | Type of secondary pump |
| Buildings.Fluid.HydronicConfigurations.Types.PumpModel | typPumMod (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.PumpModel.Speed | Type of pump model |
| Modelica.Units.SI.MassFlowRate | mPum_flow_nominal (from PartialHydronicConfiguration) | m2_flow_nominal | Pump head at design conditions |
| Modelica.Units.SI.PressureDifference | dpPum_nominal (from PartialHydronicConfiguration) | dp2_nominal + dpBal2_nominal | Pump head at design conditions |
| Controls | |||
| Buildings.Fluid.HydronicConfigurations.Types.Control | typCtl (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.Control.None | Type of built-in controls |
| Buildings.Fluid.HydronicConfigurations.Types.ControlVariable | typVar (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.ControlVariable.SupplyTemperature | Controlled variable |
| Buildings.Controls.OBC.CDL.Types.SimpleController | controllerType (from PartialHydronicConfiguration) | Buildings.Controls.OBC.CDL.Types.SimpleController.PI | Type of controller |
| Real | k (from PartialHydronicConfiguration) | 0.1 | Gain of controller |
| Real | Ti (from PartialHydronicConfiguration) | 120 | Time constant of integrator block |
| Assumptions | |||
| Boolean | use_lumFloRes (from PartialHydronicConfiguration) | true | Set to true to use a lumped flow resistance when possible |
| Boolean | allowFlowReversal (from PartialHydronicConfiguration) | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for medium 1 |
| Balancing valves | |||
| Modelica.Units.SI.PressureDifference | dpBal1_nominal (from PartialHydronicConfiguration) | 0 | Primary balancing valve pressure drop at design conditions |
| Modelica.Units.SI.PressureDifference | dpBal2_nominal (from PartialHydronicConfiguration) | 0 | Secondary balancing valve pressure drop at design conditions |
| Modelica.Units.SI.PressureDifference | dpBal3_nominal (from PartialHydronicConfiguration) | 0 | Bypass balancing valve pressure drop at design conditions |
| Dynamics › Conservation equations | |||
| Modelica.Fluid.Types.Dynamics | energyDynamics (from PartialHydronicConfiguration) | Modelica.Fluid.Types.Dynamics.FixedInitial | Type of energy balance: dynamic (3 initialization options) or steady state |
| Advanced › Diagnostics | |||
| Boolean | show_T (from PartialHydronicConfiguration) | false | = true, if actual temperature at port is computed |
Connectors
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Medium.MassFlowRate | m1_flow (from PartialHydronicConfiguration) | port_a1.m_flow | Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) |
| Modelica.Units.SI.PressureDifference | dp1 (from PartialHydronicConfiguration) | port_a1.p - port_b1.p | Pressure difference between port_a1 and port_b1 |
| Medium.MassFlowRate | m2_flow (from PartialHydronicConfiguration) | port_a2.m_flow | Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) |
| Modelica.Units.SI.PressureDifference | dp2 (from PartialHydronicConfiguration) | port_a2.p - port_b2.p | Pressure difference between port_a2 and port_b2 |
| Medium.ThermodynamicState | sta_a1 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_a1.p, noEvent(actualStream(port_a1.h_outflow)), noEvent(actualStream(port_a1.Xi_outflow))) else Medium.setState_phX(port_a1.p, inStream(port_a1.h_outflow), inStream(port_a1.Xi_outflow)) | Medium properties in port_a1 |
| Medium.ThermodynamicState | sta_b1 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_b1.p, noEvent(actualStream(port_b1.h_outflow)), noEvent(actualStream(port_b1.Xi_outflow))) else Medium.setState_phX(port_b1.p, port_b1.h_outflow, port_b1.Xi_outflow) | Medium properties in port_b1 |
| Medium.ThermodynamicState | sta_a2 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_a2.p, noEvent(actualStream(port_a2.h_outflow)), noEvent(actualStream(port_a2.Xi_outflow))) else Medium.setState_phX(port_a2.p, inStream(port_a2.h_outflow), inStream(port_a2.Xi_outflow)) | Medium properties in port_a2 |
| Medium.ThermodynamicState | sta_b2 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_b2.p, noEvent(actualStream(port_b2.h_outflow)), noEvent(actualStream(port_b2.Xi_outflow))) else Medium.setState_phX(port_b2.p, port_b2.h_outflow, port_b2.Xi_outflow) | Medium properties in port_b2 |
| Buildings.Fluid.HydronicConfigurations.Components.ThreeWayValve | val | Control valve | |
| Buildings.Fluid.FixedResistances.Junction | jun | Junction | |
| Buildings.Fluid.FixedResistances.PressureDrop | res1 | Primary balancing valve | |
| FixedResistances.PressureDrop | res3 | Bypass balancing valve |
Revisions
-
June 17, 2026, by Michael Wetter:
Updated implementation to allow a flow coefficientnthat is different from2. This allows use of the model for not fully turbulent flow.
This is for Buildings, #4620. -
June 30, 2022, by Antoine Gautier:
First implementation.