modelInjectionThreeWay
Extends from Fluid.HydronicConfigurations.Interfaces.PartialHydronicConfiguration.
Information
Summary
This configuration (see schematic below) is used for constant flow primary and consumer circuits where the consumer circuit has a different supply temperature set point, either at design conditions or varying during operation. Although this configuration may theoretically still be used if the primary and secondary design temperatures are equal, it loses its main advantage which is that the control valve can be sized for a lower flow rate and can therefore be smaller. The fixed bypass ensures a consumer circuit operation hydronically decoupled from the primary side and the control valve position.
The following table presents the main characteristics of this configuration.
| Primary circuit | Constant flow |
| Secondary (consumer) circuit | Constant flow |
| Typical applications |
Consumer circuit supply temperature different from primary circuit such
as underfloor heating systems (Otherwise use Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Decoupling) Primary pressure differential either too low or too high or varying too much |
| Non-recommended applications |
DHC systems due to the significant recirculating primary flow rate at low load Heating systems with condensing boilers for the same reason |
| Built-in valve control options |
Supply temperature Return temperature |
|
Control valve selection |
β
= ΔpA-AB / ΔpJ-AB
≈ 1 Sizing is only based on a minimum pressure drop of 3 kPa at design flow rate ṁ1, design (see below). |
| Balancing requirement |
The three-way valve should be fully open at design conditions.dpBal3_nominal=dp1_nominal-dpValve_nominal
for the primary design flow rate
ṁ1, design = ṁ2, design *
(T2, sup, design - T2, ret, design) /
(T1, sup, design - T2, ret, design)
|
|
Lumped flow resistances include (With the setting use_lumFloRes=true.)
|
Control valve val only(So the option has no effect here: the balancing valves are always modeled as distinct flow resistances.) |
Additional comments
The reduced flow through the control valve due to the intermediary bypass allows selecting a smaller valve for the same design pressure drop. The pressure drop through the control valve is compensated by the primary pump, reducing the secondary pump head.
The balancing procedure should ensure that the three-way valve is fully open at design conditions. Oversizing the primary balancing valve (yielding a lower pressure drop) is not detrimental to the consumer circuit operation: the control valve compensates by working at a lower opening fraction on average. However, the primary circuit operation is degraded with a lower ΔT and a higher mass flow rate. See Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Examples.InjectionThreeWay for a numerical illustration of those effects.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | n (from PartialHydronicConfiguration) | 2 | Flow exponent, n1=1 for laminar, n1=2 for turbulent |
| Movers.Data.Generic | perPum (from PartialHydronicConfiguration) | ||
| Configuration | |||
| Boolean | use_siz (from PartialHydronicConfiguration) | true | Set to true for built-in sizing of control valve and optional pump |
| Boolean | use_dp1 (from PartialHydronicConfiguration) | Set to true to enable dp1_nominal | |
| Boolean | use_dp2 (from PartialHydronicConfiguration) | Set to true to enable dp2_nominal | |
| Buildings.Fluid.HydronicConfigurations.Types.Valve | typVal (from PartialHydronicConfiguration) | Type of control valve | |
| Boolean | have_typVar (from PartialHydronicConfiguration) | true | Set to true to enable the choice of the controlled variable |
| Nominal condition | |||
| Modelica.Units.SI.MassFlowRate | m1_flow_nominal (from PartialHydronicConfiguration) | Mass flow rate in primary circuit at design conditions | |
| Modelica.Units.SI.MassFlowRate | m2_flow_nominal (from PartialHydronicConfiguration) | Mass flow rate in consumer circuit at design conditions | |
| Modelica.Units.SI.PressureDifference | dp1_nominal (from PartialHydronicConfiguration) | Primary circuit pressure differential at design conditions | |
| Modelica.Units.SI.PressureDifference | dp2_nominal (from PartialHydronicConfiguration) | Consumer circuit pressure differential at design conditions | |
| Control valve | |||
| Buildings.Fluid.HydronicConfigurations.Types.ValveCharacteristic | typCha (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.ValveCharacteristic.EqualPercentage | Control valve characteristic |
| Modelica.Units.SI.PressureDifference | dpValve_nominal (from PartialHydronicConfiguration) | Control valve pressure drop at design conditions | |
| Actuators.Valves.Data.Generic | flowCharacteristics (from PartialHydronicConfiguration) | Table with flow characteristics | |
| Actuators.Valves.Data.Generic | flowCharacteristics1 (from PartialHydronicConfiguration) | Table with flow characteristics for direct flow path at port_1 | |
| Actuators.Valves.Data.Generic | flowCharacteristics3 (from PartialHydronicConfiguration) | Table with flow characteristics for bypass flow path at port_3 | |
| Pump | |||
| Buildings.Fluid.HydronicConfigurations.Types.Pump | typPum (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.Pump.VariableInput | Type of secondary pump |
| Buildings.Fluid.HydronicConfigurations.Types.PumpModel | typPumMod (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.PumpModel.Speed | Type of pump model |
| Modelica.Units.SI.MassFlowRate | mPum_flow_nominal (from PartialHydronicConfiguration) | m2_flow_nominal | Pump head at design conditions |
| Modelica.Units.SI.PressureDifference | dpPum_nominal (from PartialHydronicConfiguration) | dp2_nominal + dpBal2_nominal | Pump head at design conditions |
| Controls | |||
| Buildings.Fluid.HydronicConfigurations.Types.Control | typCtl (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.Control.None | Type of built-in controls |
| Buildings.Fluid.HydronicConfigurations.Types.ControlVariable | typVar (from PartialHydronicConfiguration) | Buildings.Fluid.HydronicConfigurations.Types.ControlVariable.SupplyTemperature | Controlled variable |
| Buildings.Controls.OBC.CDL.Types.SimpleController | controllerType (from PartialHydronicConfiguration) | Buildings.Controls.OBC.CDL.Types.SimpleController.PI | Type of controller |
| Real | k (from PartialHydronicConfiguration) | 0.1 | Gain of controller |
| Real | Ti (from PartialHydronicConfiguration) | 120 | Time constant of integrator block |
| Assumptions | |||
| Boolean | use_lumFloRes (from PartialHydronicConfiguration) | true | Set to true to use a lumped flow resistance when possible |
| Boolean | allowFlowReversal (from PartialHydronicConfiguration) | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for medium 1 |
| Balancing valves | |||
| Modelica.Units.SI.PressureDifference | dpBal1_nominal (from PartialHydronicConfiguration) | 0 | Primary balancing valve pressure drop at design conditions |
| Modelica.Units.SI.PressureDifference | dpBal2_nominal (from PartialHydronicConfiguration) | 0 | Secondary balancing valve pressure drop at design conditions |
| Modelica.Units.SI.PressureDifference | dpBal3_nominal (from PartialHydronicConfiguration) | 0 | Bypass balancing valve pressure drop at design conditions |
| Dynamics › Conservation equations | |||
| Modelica.Fluid.Types.Dynamics | energyDynamics (from PartialHydronicConfiguration) | Modelica.Fluid.Types.Dynamics.FixedInitial | Type of energy balance: dynamic (3 initialization options) or steady state |
| Advanced › Diagnostics | |||
| Boolean | show_T (from PartialHydronicConfiguration) | false | = true, if actual temperature at port is computed |
Connectors
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Medium.MassFlowRate | m1_flow (from PartialHydronicConfiguration) | port_a1.m_flow | Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) |
| Modelica.Units.SI.PressureDifference | dp1 (from PartialHydronicConfiguration) | port_a1.p - port_b1.p | Pressure difference between port_a1 and port_b1 |
| Medium.MassFlowRate | m2_flow (from PartialHydronicConfiguration) | port_a2.m_flow | Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) |
| Modelica.Units.SI.PressureDifference | dp2 (from PartialHydronicConfiguration) | port_a2.p - port_b2.p | Pressure difference between port_a2 and port_b2 |
| Medium.ThermodynamicState | sta_a1 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_a1.p, noEvent(actualStream(port_a1.h_outflow)), noEvent(actualStream(port_a1.Xi_outflow))) else Medium.setState_phX(port_a1.p, inStream(port_a1.h_outflow), inStream(port_a1.Xi_outflow)) | Medium properties in port_a1 |
| Medium.ThermodynamicState | sta_b1 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_b1.p, noEvent(actualStream(port_b1.h_outflow)), noEvent(actualStream(port_b1.Xi_outflow))) else Medium.setState_phX(port_b1.p, port_b1.h_outflow, port_b1.Xi_outflow) | Medium properties in port_b1 |
| Medium.ThermodynamicState | sta_a2 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_a2.p, noEvent(actualStream(port_a2.h_outflow)), noEvent(actualStream(port_a2.Xi_outflow))) else Medium.setState_phX(port_a2.p, inStream(port_a2.h_outflow), inStream(port_a2.Xi_outflow)) | Medium properties in port_a2 |
| Medium.ThermodynamicState | sta_b2 (from PartialHydronicConfiguration) | if allowFlowReversal then Medium.setState_phX(port_b2.p, noEvent(actualStream(port_b2.h_outflow)), noEvent(actualStream(port_b2.Xi_outflow))) else Medium.setState_phX(port_b2.p, port_b2.h_outflow, port_b2.Xi_outflow) | Medium properties in port_b2 |
| Buildings.Fluid.HydronicConfigurations.Components.ThreeWayValve | val | Control valve | |
| FixedResistances.Junction | jun | Junction | |
| FixedResistances.Junction | junBypSup | Junction | |
| FixedResistances.Junction | junBypRet | Junction | |
| FixedResistances.PressureDrop | res1 | Primary balancing valve | |
| FixedResistances.PressureDrop | res2 | Secondary balancing valve | |
| Buildings.Fluid.HydronicConfigurations.Components.Pump | pum | Pump | |
| Sensors.TemperatureTwoPort | T2Sup | Consumer circuit supply temperature sensor | |
| Controls.PIDWithOperatingMode | ctl | Controller | |
| Buildings.Controls.OBC.CDL.Integers.GreaterThreshold | isEna | Returns true if enabled | |
| Sensors.TemperatureTwoPort | T2Ret | Consumer circuit return temperature sensor | |
| Buildings.Controls.OBC.CDL.Routing.RealExtractor | extIndSig | Select measured signal | |
| Buildings.Controls.OBC.CDL.Integers.Sources.Constant | ctlVar | Controlled variable selector |
Revisions
-
June 17, 2026, by Michael Wetter:
Updated implementation to allow a flow coefficientnthat is different from2. This allows use of the model for not fully turbulent flow.
This is for Buildings, #4620. -
June 30, 2022, by Antoine Gautier:
First implementation.