modelSingleMixing

Single mixing circuit

Extends from Fluid.HydronicConfigurations.Interfaces.PartialHydronicConfiguration.

Information

Variable primary

This is a typical configuration for constant flow secondary circuits that have a design supply temperature identical to the primary circuit. The control valve should be sized with a pressure drop at least equal to the maximum of Δp1 and 3e3 Pa. Its authority is β = ΔpA-AB / (ΔpA-AB + Δp1).

In most cases the bypass balancing valve is not needed. However, it may be needed to counter negative back pressure created by other served circuits.

Parameterization

By default the secondary pump is parameterized with m2_flow_nominal and dp2_nominal + dpBal2_nominal + max({val.dpValve_nominal, val.dp3Valve_nominal}) + dpBal3_nominal at maximum speed.

Parameters

TypeNameDefaultDescription
Realn (from PartialHydronicConfiguration)2Flow exponent, n1=1 for laminar, n1=2 for turbulent
Movers.Data.GenericperPum (from PartialHydronicConfiguration)
Configuration
Booleanuse_siz (from PartialHydronicConfiguration)trueSet to true for built-in sizing of control valve and optional pump
Booleanuse_dp1 (from PartialHydronicConfiguration)Set to true to enable dp1_nominal
Booleanuse_dp2 (from PartialHydronicConfiguration)Set to true to enable dp2_nominal
Buildings.Fluid.HydronicConfigurations.Types.ValvetypVal (from PartialHydronicConfiguration)Type of control valve
Booleanhave_typVar (from PartialHydronicConfiguration)trueSet to true to enable the choice of the controlled variable
Nominal condition
Modelica.Units.SI.MassFlowRatem1_flow_nominal (from PartialHydronicConfiguration)Mass flow rate in primary circuit at design conditions
Modelica.Units.SI.MassFlowRatem2_flow_nominal (from PartialHydronicConfiguration)Mass flow rate in consumer circuit at design conditions
Modelica.Units.SI.PressureDifferencedp1_nominal (from PartialHydronicConfiguration)Primary circuit pressure differential at design conditions
Modelica.Units.SI.PressureDifferencedp2_nominal (from PartialHydronicConfiguration)Consumer circuit pressure differential at design conditions
Control valve
Buildings.Fluid.HydronicConfigurations.Types.ValveCharacteristictypCha (from PartialHydronicConfiguration)Buildings.Fluid.HydronicConfigurations.Types.ValveCharacteristic.EqualPercentageControl valve characteristic
Modelica.Units.SI.PressureDifferencedpValve_nominal (from PartialHydronicConfiguration)Control valve pressure drop at design conditions
Actuators.Valves.Data.GenericflowCharacteristics (from PartialHydronicConfiguration)Table with flow characteristics
Actuators.Valves.Data.GenericflowCharacteristics1 (from PartialHydronicConfiguration)Table with flow characteristics for direct flow path at port_1
Actuators.Valves.Data.GenericflowCharacteristics3 (from PartialHydronicConfiguration)Table with flow characteristics for bypass flow path at port_3
Pump
Buildings.Fluid.HydronicConfigurations.Types.PumptypPum (from PartialHydronicConfiguration)Buildings.Fluid.HydronicConfigurations.Types.Pump.VariableInputType of secondary pump
Buildings.Fluid.HydronicConfigurations.Types.PumpModeltypPumMod (from PartialHydronicConfiguration)Buildings.Fluid.HydronicConfigurations.Types.PumpModel.SpeedType of pump model
Modelica.Units.SI.MassFlowRatemPum_flow_nominal (from PartialHydronicConfiguration)m2_flow_nominalPump head at design conditions
Modelica.Units.SI.PressureDifferencedpPum_nominal (from PartialHydronicConfiguration)dp2_nominal + dpBal2_nominalPump head at design conditions
Controls
Buildings.Fluid.HydronicConfigurations.Types.ControltypCtl (from PartialHydronicConfiguration)Buildings.Fluid.HydronicConfigurations.Types.Control.NoneType of built-in controls
Buildings.Fluid.HydronicConfigurations.Types.ControlVariabletypVar (from PartialHydronicConfiguration)Buildings.Fluid.HydronicConfigurations.Types.ControlVariable.SupplyTemperatureControlled variable
Buildings.Controls.OBC.CDL.Types.SimpleControllercontrollerType (from PartialHydronicConfiguration)Buildings.Controls.OBC.CDL.Types.SimpleController.PIType of controller
Realk (from PartialHydronicConfiguration)0.1Gain of controller
RealTi (from PartialHydronicConfiguration)120Time constant of integrator block
Assumptions
Booleanuse_lumFloRes (from PartialHydronicConfiguration)trueSet to true to use a lumped flow resistance when possible
BooleanallowFlowReversal (from PartialHydronicConfiguration)true= false to simplify equations, assuming, but not enforcing, no flow reversal for medium 1
Balancing valves
Modelica.Units.SI.PressureDifferencedpBal1_nominal (from PartialHydronicConfiguration)0Primary balancing valve pressure drop at design conditions
Modelica.Units.SI.PressureDifferencedpBal2_nominal (from PartialHydronicConfiguration)0Secondary balancing valve pressure drop at design conditions
Modelica.Units.SI.PressureDifferencedpBal3_nominal (from PartialHydronicConfiguration)0Bypass balancing valve pressure drop at design conditions
Dynamics › Conservation equations
Modelica.Fluid.Types.DynamicsenergyDynamics (from PartialHydronicConfiguration)Modelica.Fluid.Types.Dynamics.FixedInitialType of energy balance: dynamic (3 initialization options) or steady state
Advanced › Diagnostics
Booleanshow_T (from PartialHydronicConfiguration)false= true, if actual temperature at port is computed

Connectors

TypeNameDefaultDescription
Modelica.Fluid.Interfaces.FluidPort_aport_a1 (from PartialHydronicConfiguration)Primary supply port
Modelica.Fluid.Interfaces.FluidPort_bport_b1 (from PartialHydronicConfiguration)Primary return port
Modelica.Fluid.Interfaces.FluidPort_aport_a2 (from PartialHydronicConfiguration)Secondary return port
Modelica.Fluid.Interfaces.FluidPort_bport_b2 (from PartialHydronicConfiguration)Secondary supply port
Buildings.Controls.OBC.CDL.Interfaces.RealInputyVal (from PartialHydronicConfiguration)Valve control signal
Buildings.Controls.OBC.CDL.Interfaces.RealInputset (from PartialHydronicConfiguration)Set point
Buildings.Controls.OBC.CDL.Interfaces.RealInputyPum (from PartialHydronicConfiguration)Pump control signal (variable speed)
Buildings.Controls.OBC.CDL.Interfaces.IntegerInputmode (from PartialHydronicConfiguration)Operating mode
Buildings.Controls.OBC.CDL.Interfaces.RealOutputyVal_actual (from PartialHydronicConfiguration)Valve position feedback
Buildings.Controls.OBC.CDL.Interfaces.RealOutputyPum_actual (from PartialHydronicConfiguration)Actual pump input value that is used for computations
Buildings.Controls.OBC.CDL.Interfaces.RealOutputPPum (from PartialHydronicConfiguration)Pump electrical power

Components

TypeNameDefaultDescription
Medium.MassFlowRatem1_flow (from PartialHydronicConfiguration)port_a1.m_flowMass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction)
Modelica.Units.SI.PressureDifferencedp1 (from PartialHydronicConfiguration)port_a1.p - port_b1.pPressure difference between port_a1 and port_b1
Medium.MassFlowRatem2_flow (from PartialHydronicConfiguration)port_a2.m_flowMass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction)
Modelica.Units.SI.PressureDifferencedp2 (from PartialHydronicConfiguration)port_a2.p - port_b2.pPressure difference between port_a2 and port_b2
Medium.ThermodynamicStatesta_a1 (from PartialHydronicConfiguration)if allowFlowReversal then Medium.setState_phX(port_a1.p, noEvent(actualStream(port_a1.h_outflow)), noEvent(actualStream(port_a1.Xi_outflow))) else Medium.setState_phX(port_a1.p, inStream(port_a1.h_outflow), inStream(port_a1.Xi_outflow))Medium properties in port_a1
Medium.ThermodynamicStatesta_b1 (from PartialHydronicConfiguration)if allowFlowReversal then Medium.setState_phX(port_b1.p, noEvent(actualStream(port_b1.h_outflow)), noEvent(actualStream(port_b1.Xi_outflow))) else Medium.setState_phX(port_b1.p, port_b1.h_outflow, port_b1.Xi_outflow)Medium properties in port_b1
Medium.ThermodynamicStatesta_a2 (from PartialHydronicConfiguration)if allowFlowReversal then Medium.setState_phX(port_a2.p, noEvent(actualStream(port_a2.h_outflow)), noEvent(actualStream(port_a2.Xi_outflow))) else Medium.setState_phX(port_a2.p, inStream(port_a2.h_outflow), inStream(port_a2.Xi_outflow))Medium properties in port_a2
Medium.ThermodynamicStatesta_b2 (from PartialHydronicConfiguration)if allowFlowReversal then Medium.setState_phX(port_b2.p, noEvent(actualStream(port_b2.h_outflow)), noEvent(actualStream(port_b2.Xi_outflow))) else Medium.setState_phX(port_b2.p, port_b2.h_outflow, port_b2.Xi_outflow)Medium properties in port_b2
Buildings.Fluid.HydronicConfigurations.Components.ThreeWayValvevalControl valve
FixedResistances.JunctionjunJunction
FixedResistances.PressureDropres1Primary balancing valve
FixedResistances.PressureDropres2Secondary balancing valve
Buildings.Fluid.HydronicConfigurations.Components.PumppumPump
Sensors.TemperatureTwoPortT2SupConsumer circuit supply temperature sensor
Controls.PIDWithOperatingModectlController
Buildings.Controls.OBC.CDL.Integers.GreaterThresholdisEnaReturns true if enabled
Sensors.TemperatureTwoPortT2RetConsumer circuit return temperature sensor
FixedResistances.PressureDropres3Bypass balancing valve

Revisions

  • June 17, 2026, by Michael Wetter:
    Updated implementation to allow a flow coefficient n that is different from 2. This allows use of the model for not fully turbulent flow.
    This is for Buildings, #4620.