modelSpecificEnthalpyTwoPort

Ideal two port sensor for the specific enthalpy

Extends from Buildings.Fluid.Sensors.BaseClasses.PartialDynamicFlowSensor (Partial component to model sensors that measure flow properties using a dynamic model), Modelica.Icons.RoundSensor (Icon representing a round measurement device).

Information

This model outputs the specific enthalpy of a passing fluid. The sensor is ideal, i.e. it does not influence the fluid. If the parameter tau is non-zero, then its output is computed using a first order differential equation. Setting tau=0 is not recommend. See Buildings.Fluid.Sensors.UsersGuide for an explanation.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.Timetau (from PartialDynamicFlowSensor)1Time constant at nominal flow rate (use tau=0 for steady-state sensor, but see user guide for potential problems)
Assumptions
BooleanallowFlowReversal (from PartialTwoPort)true= false to simplify equations, assuming, but not enforcing, no flow reversal
Nominal condition
Modelica.Units.SI.MassFlowRatem_flow_nominal (from PartialFlowSensor)Nominal mass flow rate, used for regularization near zero flow
Advanced
Modelica.Units.SI.MassFlowRatem_flow_small (from PartialFlowSensor)1E-4*m_flow_nominalFor bi-directional flow, temperature is regularized in the region |m_flow| < m_flow_small (m_flow_small > 0 required)
Initialization
Modelica.Blocks.Types.InitinitType (from PartialDynamicFlowSensor)Modelica.Blocks.Types.Init.InitialStateType of initialization (InitialState and InitialOutput are identical)
Modelica.Units.SI.SpecificEnthalpyh_out_startMedium.specificEnthalpy_pTX(p = Medium.p_default, T = Medium.T_default, X = Medium.X_default)Initial or guess value of output (= state)

Connectors

TypeNameDefaultDescription
Modelica.Fluid.Interfaces.FluidPort_aport_a (from PartialTwoPort)Fluid connector a (positive design flow direction is from port_a to port_b)
Modelica.Fluid.Interfaces.FluidPort_bport_b (from PartialTwoPort)Fluid connector b (positive design flow direction is from port_a to port_b)
Modelica.Blocks.Interfaces.RealOutputh_outSpecific enthalpy of the passing fluid

Revisions

  • June 25, 2026, by Michael Wetter:
    Added nominal attribute to state variable.
    This is for IBPSA, #2132.
  • February 25, 2020, by Michael Wetter:
    Changed icon to display its operating state.
    This is for #1294.
  • January 18, 2016 by Filip Jorissen:
    Using parameter tauInv since this now exists in Buildings.Fluid.Sensors.BaseClasses.PartialDynamicFlowSensor. This is for #372.
  • June 3, 2011 by Michael Wetter:
    Revised implementation to add dynamics in such a way that the time constant increases as the mass flow rate tends to zero. This significantly improves the numerics.
  • September 29, 2009, by Michael Wetter:
    First implementation.