modelDamperValves

Validate model for controlling damper and valve position of VAV reheat terminal unit

Information

This example validates Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.Reheat.DamperValves for damper and valve control of VAV reheat terminal unit.

Components

TypeNameDefaultDescription
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.Reheat.DamperValvesdamValOutput signal for controlling VAV reheat box damper and valve position
Buildings.Controls.OBC.CDL.Reals.Sources.RampuHeaHeating control signal
Buildings.Controls.OBC.CDL.Reals.Sources.RampuCooCooling control signal
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTHeaSetZone heating setpoint temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTZonZone temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTSupAHU supply air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActMin_flowActive minimum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActHeaMin_flowActive heating minimum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActHeaMax_flowActive heating maximum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActCooMin_flowActive cooling minimum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActCooMax_flowActive cooling maximum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.SinVDis_flowDischarge airflow rate
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTDisDischarge air temperature
Buildings.Controls.OBC.CDL.Integers.Sources.ConstantoccSigOccupied signal

Revisions

  • Spetember 10, 2017, by Jianjun Hu:
    First implementation.