blockMerkel
Model for thermal performance of Merkel cooling tower
Extends from Buildings.Obsolete.BaseClasses.ObsoleteModel (Icon for classes that are obsolete and will be removed in later versions), Modelica.Blocks.Icons.Block (Basic graphical layout of input/output block).
Information
Model for the thermal peformance of the Merkel cooling tower.
For the documentation, see Buildings.Obsolete.Fluid.HeatExchangers.CoolingTowers.Merkel.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Obsolete.Fluid.HeatExchangers.CoolingTowers.Data.UAMerkel | UACor | ||
| Modelica.Units.SI.HeatFlowRate | Q_flow_nominal | -m_flow_nominal*cpWat_nominal*(TWatIn_nominal - TWatOut_nominal) | Nominal heat transfer, (negative) |
| Modelica.Units.SI.ThermalConductance | UA_nominal | NTU_nominal*CMin_flow_nominal*Buildings.Utilities.Psychrometrics.Constants.cpAir/cpEqu_nominal | Thermal conductance at nominal flow, used to compute heat capacity |
| Real | eps_nominal | Q_flow_nominal/((TAirInWB_nominal - TWatIn_nominal)*CMin_flow_nominal) | Nominal heat transfer effectiveness |
| Real | NTU_nominal | Buildings.Fluid.HeatExchangers.BaseClasses.ntu_epsilonZ(eps = min(1, max(0, eps_nominal)), Z = Z_nominal, flowRegime = Integer(Buildings.Fluid.Types.HeatExchangerConfiguration.CounterFlow)) | Nominal number of transfer units |
| Nominal condition | |||
| Modelica.Units.SI.MassFlowRate | m_flow_nominal | Nominal mass flow rate of water | |
| Real | ratWatAir_nominal | Water-to-air mass flow rate ratio at design condition | |
| Fan | |||
| Modelica.Units.SI.MassFlowRate | mAir_flow_nominal | m_flow_nominal/ratWatAir_nominal | Nominal mass flow rate of air |
| Real | yMin | Minimum control signal until fan is switched off (used for smoothing between forced and free convection regime) | |
| Heat transfer | |||
| Modelica.Units.SI.Temperature | TAirInWB_nominal | Nominal outdoor (air inlet) wetbulb temperature | |
| Modelica.Units.SI.Temperature | TWatIn_nominal | Nominal water inlet temperature | |
| Modelica.Units.SI.Temperature | TWatOut_nominal | Nominal water outlet temperature | |
| Real | fraFreCon | Fraction of tower capacity in free convection regime | |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Interfaces.RealInput | y | Fan control signal | |
| Modelica.Blocks.Interfaces.RealInput | m_flow | Water mass flow rate | |
| Modelica.Blocks.Interfaces.RealInput | TWatIn | Inlet water temperature | |
| Modelica.Blocks.Interfaces.RealInput | TAir | Entering air wet bulb temperature | |
| Modelica.Blocks.Interfaces.RealOutput | Q_flow | Heat removed from water |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Temperature | TAirOut | Outlet air temperature | |
| Modelica.Units.SI.MassFlowRate | mAir_flow | Air mass flow rate | |
| Modelica.Units.SI.MassFraction | FRWat | Ratio actual over design water mass flow ratio | |
| Modelica.Units.SI.MassFraction | FRAir | Ratio actual over design air mass flow ratio | |
| Real | eps | Heat exchanger effectiveness | |
| Modelica.Units.SI.SpecificHeatCapacity | cpWat | Heat capacity of water | |
| Modelica.Units.SI.ThermalConductance | CAir_flow | Heat capacity flow rate of air | |
| Modelica.Units.SI.ThermalConductance | CWat_flow | Heat capacity flow rate of water | |
| Modelica.Units.SI.ThermalConductance | CMin_flow | Minimum heat capacity flow rate | |
| Modelica.Units.SI.HeatFlowRate | QMax_flow | Maximum heat flow rate into air | |
| Modelica.Units.SI.ThermalConductance | UAe | Thermal conductance for equivalent fluid | |
| Modelica.Units.SI.ThermalConductance | UA | Thermal conductance |
Contents
| Name | Description |
|---|---|
| Medium in the component | |
| Package of medium air |
Revisions
-
April 27, 2026, by Michael Wetter:
Moved toObsoletepackage due to new cooling tower implementation.
This is for issue 4567. -
April 17, 2025, by Michael Wetter:
Corrected computation of nominal UA value, which also needs to include the correction forcpEqu_nominal.
This is for #4189. -
January 20, 2020, by Michael Wetter:
First implementation during refactoring of Buildings.Obsolete.Fluid.HeatExchangers.CoolingTowers.Merkel.