blockMerkel

Model for thermal performance of Merkel cooling tower

Extends from Buildings.Obsolete.BaseClasses.ObsoleteModel (Icon for classes that are obsolete and will be removed in later versions), Modelica.Blocks.Icons.Block (Basic graphical layout of input/output block).

Information

Model for the thermal peformance of the Merkel cooling tower.

For the documentation, see Buildings.Obsolete.Fluid.HeatExchangers.CoolingTowers.Merkel.

Parameters

TypeNameDefaultDescription
Buildings.Obsolete.Fluid.HeatExchangers.CoolingTowers.Data.UAMerkelUACor
Modelica.Units.SI.HeatFlowRateQ_flow_nominal-m_flow_nominal*cpWat_nominal*(TWatIn_nominal - TWatOut_nominal)Nominal heat transfer, (negative)
Modelica.Units.SI.ThermalConductanceUA_nominalNTU_nominal*CMin_flow_nominal*Buildings.Utilities.Psychrometrics.Constants.cpAir/cpEqu_nominalThermal conductance at nominal flow, used to compute heat capacity
Realeps_nominalQ_flow_nominal/((TAirInWB_nominal - TWatIn_nominal)*CMin_flow_nominal)Nominal heat transfer effectiveness
RealNTU_nominalBuildings.Fluid.HeatExchangers.BaseClasses.ntu_epsilonZ(eps = min(1, max(0, eps_nominal)), Z = Z_nominal, flowRegime = Integer(Buildings.Fluid.Types.HeatExchangerConfiguration.CounterFlow))Nominal number of transfer units
Nominal condition
Modelica.Units.SI.MassFlowRatem_flow_nominalNominal mass flow rate of water
RealratWatAir_nominalWater-to-air mass flow rate ratio at design condition
Fan
Modelica.Units.SI.MassFlowRatemAir_flow_nominalm_flow_nominal/ratWatAir_nominalNominal mass flow rate of air
RealyMinMinimum control signal until fan is switched off (used for smoothing between forced and free convection regime)
Heat transfer
Modelica.Units.SI.TemperatureTAirInWB_nominalNominal outdoor (air inlet) wetbulb temperature
Modelica.Units.SI.TemperatureTWatIn_nominalNominal water inlet temperature
Modelica.Units.SI.TemperatureTWatOut_nominalNominal water outlet temperature
RealfraFreConFraction of tower capacity in free convection regime

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputyFan control signal
Modelica.Blocks.Interfaces.RealInputm_flowWater mass flow rate
Modelica.Blocks.Interfaces.RealInputTWatInInlet water temperature
Modelica.Blocks.Interfaces.RealInputTAirEntering air wet bulb temperature
Modelica.Blocks.Interfaces.RealOutputQ_flowHeat removed from water

Components

TypeNameDefaultDescription
Modelica.Units.SI.TemperatureTAirOutOutlet air temperature
Modelica.Units.SI.MassFlowRatemAir_flowAir mass flow rate
Modelica.Units.SI.MassFractionFRWatRatio actual over design water mass flow ratio
Modelica.Units.SI.MassFractionFRAirRatio actual over design air mass flow ratio
RealepsHeat exchanger effectiveness
Modelica.Units.SI.SpecificHeatCapacitycpWatHeat capacity of water
Modelica.Units.SI.ThermalConductanceCAir_flowHeat capacity flow rate of air
Modelica.Units.SI.ThermalConductanceCWat_flowHeat capacity flow rate of water
Modelica.Units.SI.ThermalConductanceCMin_flowMinimum heat capacity flow rate
Modelica.Units.SI.HeatFlowRateQMax_flowMaximum heat flow rate into air
Modelica.Units.SI.ThermalConductanceUAeThermal conductance for equivalent fluid
Modelica.Units.SI.ThermalConductanceUAThermal conductance

Contents

NameDescription
MediumMedium in the component
AirprotectedPackage of medium air

Revisions

  • April 27, 2026, by Michael Wetter:
    Moved to Obsolete package due to new cooling tower implementation.
    This is for issue 4567.
  • April 17, 2025, by Michael Wetter:
    Corrected computation of nominal UA value, which also needs to include the correction for cpEqu_nominal.
    This is for #4189.
  • January 20, 2020, by Michael Wetter:
    First implementation during refactoring of Buildings.Obsolete.Fluid.HeatExchangers.CoolingTowers.Merkel.