recordCoil

Record for coil model

Extends from Modelica.Icons.Record (Icon for records).

Information

This record provides the set of sizing parameters for the classes within Buildings.Templates.Components.Coils.

Parameters

TypeNameDefaultDescription
Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Carrier_Centurion_50PG06datCoi
Configuration
Buildings.Templates.Components.Types.CoiltypEquipment type
Buildings.Templates.Components.Types.ValvetypValType of valve
Nominal condition
Modelica.Units.SI.MassFlowRatemAir_flow_nominalAir mass flow rate
Modelica.Units.SI.PressureDifferencedpAir_nominalAir pressure drop
Modelica.Units.SI.MassFlowRatemWat_flow_nominalLiquid mass flow rate
Modelica.Units.SI.PressureDifferencedpWat_nominalLiquid pressure drop across coil
Modelica.Units.SI.PressureDifferencedpValve_nominalLiquid pressure drop across fully open valve
Modelica.Units.SI.HeatFlowRatecap_nominalCoil capacity
Modelica.Units.SI.HeatFlowRateQ_flow_nominalif typ == Buildings.Templates.Components.Types.Coil.WaterBasedHeating or typ == Buildings.Templates.Components.Types.Coil.ElectricHeating then abs(cap_nominal) else -1*abs(cap_nominal)Nominal heat flow rate
Modelica.Units.SI.TemperatureTWatEnt_nominalNominal entering liquid temperature
Modelica.Units.SI.TemperatureTAirEnt_nominalNominal entering air temperature
Modelica.Units.SI.MassFractionwAirEnt_nominalNominal entering air humidity ratio