| Buildings.Templates.Plants.Controls.HeatPumps.AirToWater | ctl | | Plant controller |
| Buildings.Controls.OBC.CDL.Reals.Sources.TimeTable | ratV_flow | | Source signal for volume flow rate ratio – Index 1 for HW, 2 for CHW |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | dTHeaWat | | HW Delta-T |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | dTChiWat | | CHW Delta-T |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | VHeaWat_flow | | Scale by design flow |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | VChiWat_flow | | Scale by design flow |
| Components.Controls.StatusEmulator[ctl.nHp] | y1Hp_actual | | HP status |
| Components.Controls.StatusEmulator[ctl.nPumHeaWatPri] | y1PumHeaWatPri_actual1 | | Primary HW pump status |
| Components.Controls.StatusEmulator[ctl.nPumChiWatPri] | y1PumChiWatPri_actual | | Primary CHW pump status |
| Components.Controls.StatusEmulator[ctl.nPumHeaWatSec] | y1PumHeaWatSec_actual | | Secondary HW pump status |
| Components.Controls.StatusEmulator[ctl.nPumChiWatSec] | y1PumChiWatSec_actual | | Secondary CHW pump status |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin | TOut | | OAT |
| Buildings.Controls.OBC.CDL.Reals.GreaterThreshold | isDemHea | | Return true if heating demand |
| Buildings.Controls.OBC.CDL.Reals.GreaterThreshold | isDemCoo | | Return true if cooling demand |
| Buildings.Controls.OBC.CDL.Conversions.BooleanToInteger | reqPlaHeaWat | | Generate HW plant request |
| Buildings.Controls.OBC.CDL.Conversions.BooleanToInteger | reqPlaChiWat | | Generate CHW plant request |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter[2] | gai | | Use fraction of flow rate as a proxy for plant reset request |
| Buildings.Controls.OBC.CDL.Conversions.RealToInteger | reqResHeaWat | | Generate HW reset request |
| Buildings.Controls.OBC.CDL.Conversions.RealToInteger | reqResChiWat | | Generate CHW reset request |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin[1] | sin | | Source signal used to generate measurement values |
| Buildings.Controls.OBC.CDL.Reals.Add[1] | dpHeaWatRem | | Differential pressure at remote location |
| Buildings.Controls.OBC.CDL.Reals.Add[1] | dpChiWatRem | | Differential pressure at remote location |
| Pumps.Generic.ResetLocalDifferentialPressure[1] | resDpHeaWatLoc | | Local HW DP reset |
| Pumps.Generic.ResetLocalDifferentialPressure[1] | resDpChiWatLoc | | Local CHW DP reset |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin[1] | sin1 | | Source signal used to generate measurement values |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | dpHeaWatLoc | | Differential pressure local to the plant |
| Buildings.Controls.OBC.CDL.Reals.MultiplyByParameter | dpChiWatLoc | | Differential pressure local to the plant |
| Components.Controls.StatusEmulator | y1Hrc_actual | | Sidestream HRC status |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | dTHeaWatUpsHrc | | HW Delta-T as measured upstream of HRC |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | dTChiWatUpsHrc | | CHW Delta-T as measured upstream of HRC |
| Buildings.Controls.OBC.CDL.Reals.Add | THeaWatRet | | HWRT |
| Buildings.Controls.OBC.CDL.Reals.Add | THeaWatRetUpsHrc | | HWRT upstream of HRC |
| Buildings.Controls.OBC.CDL.Reals.Add | TChiWatRet | | CHWRT |
| Buildings.Controls.OBC.CDL.Reals.Add | TChiWatRetUpsHrc | | CHWRT upstream of HRC |