recordVAVBoxController

Record for VAV terminal unit controller

Extends from Buildings.Templates.ZoneEquipment.Components.Data.PartialController (Record for controller interface class).

Information

This record provides the set of sizing and operating parameters for VAV box controllers within Buildings.Templates.ZoneEquipment.Components.Controls.

Parameters

TypeNameDefaultDescription
Configuration
Buildings.Templates.ZoneEquipment.Types.Controllertyp (from PartialController)Type of controller
Energy and ventilation standards
Buildings.Controls.OBC.ASHRAE.G36.Types.VentilationStandardstdVenVentilation standard
Ventilation
Modelica.Units.SI.VolumeFlowRateVOutMinOcc_flowZone minimum outdoor airflow for occupants
Modelica.Units.SI.VolumeFlowRateVOutMinAre_flowZone minimum outdoor airflow for building area
RealVOutAre_flowArea component of the breathing zone outdoor airflow
RealVOutOcc_flowPopulation component of the breathing zone outdoor airflow
RealeffAirDisHea0.8Zone air distribution effectiveness during heating
RealeffAirDisCoo1.0Zone air distribution effectiveness during cooling
Temperature
Modelica.Units.SI.TemperatureDifferencedTAirDisHea_max11Zone maximum discharge air temperature above heating setpoint
Airflow
Modelica.Units.SI.VolumeFlowRateVAirCooSet_flow_maxZone maximum cooling airflow setpoint
Modelica.Units.SI.VolumeFlowRateVAirSet_flow_minZone minimum airflow setpoint
Modelica.Units.SI.VolumeFlowRateVAirHeaSet_flow_maxZone maximum heating airflow setpoint
Modelica.Units.SI.VolumeFlowRateVAirHeaSet_flow_min0Zone minimum heating airflow setpoint