recordVAVBoxController
Record for VAV terminal unit controller
Extends from Buildings.Templates.ZoneEquipment.Components.Data.PartialController (Record for controller interface class).
Information
This record provides the set of sizing and operating parameters for VAV box controllers within Buildings.Templates.ZoneEquipment.Components.Controls.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Configuration | |||
| Buildings.Templates.ZoneEquipment.Types.Controller | typ (from PartialController) | Type of controller | |
| Energy and ventilation standards | |||
| Buildings.Controls.OBC.ASHRAE.G36.Types.VentilationStandard | stdVen | Ventilation standard | |
| Ventilation | |||
| Modelica.Units.SI.VolumeFlowRate | VOutMinOcc_flow | Zone minimum outdoor airflow for occupants | |
| Modelica.Units.SI.VolumeFlowRate | VOutMinAre_flow | Zone minimum outdoor airflow for building area | |
| Real | VOutAre_flow | Area component of the breathing zone outdoor airflow | |
| Real | VOutOcc_flow | Population component of the breathing zone outdoor airflow | |
| Real | effAirDisHea | 0.8 | Zone air distribution effectiveness during heating |
| Real | effAirDisCoo | 1.0 | Zone air distribution effectiveness during cooling |
| Temperature | |||
| Modelica.Units.SI.TemperatureDifference | dTAirDisHea_max | 11 | Zone maximum discharge air temperature above heating setpoint |
| Airflow | |||
| Modelica.Units.SI.VolumeFlowRate | VAirCooSet_flow_max | Zone maximum cooling airflow setpoint | |
| Modelica.Units.SI.VolumeFlowRate | VAirSet_flow_min | Zone minimum airflow setpoint | |
| Modelica.Units.SI.VolumeFlowRate | VAirHeaSet_flow_max | Zone maximum heating airflow setpoint | |
| Modelica.Units.SI.VolumeFlowRate | VAirHeaSet_flow_min | 0 | Zone minimum heating airflow setpoint |