modelVAVBoxReheat

VAV terminal unit with reheat

Extends from Buildings.Templates.ZoneEquipment.Interfaces.VAVBox (Interface class for VAV terminal unit).

Information

Description

This template represents a VAV terminal unit with reheat.

The possible configuration options are enumerated in the table below. The user may refer to ASHRAE (2021) for further details. The first option displayed in bold characters corresponds to the default configuration.

Configuration parameterOptionsNotes
VAV damper Modulating damper
Reheat coil Hot water coil with two-way valve
Modulating electric heating coil
Controller ASHRAE Guideline 36 controller An open loop controller is also available for validation purposes only.

References

  • ASHRAE, 2021. Guideline 36-2021, High-Performance Sequences of Operation for HVAC Systems. Atlanta, GA.

Parameters

TypeNameDefaultDescription
Buildings.Templates.ZoneEquipment.Configuration.PartialAirTerminalcfg (from PartialAirTerminal)Configuration parameters
Buildings.Templates.ZoneEquipment.Data.PartialAirTerminaldat (from PartialAirTerminal)Design and operating parameters
Configuration
Buildings.Templates.ZoneEquipment.Types.Configurationtyp (from PartialAirTerminal)Type of system
Stringid (from PartialAirTerminal)dat.idSystem tag
Booleanhave_souChiWat (from PartialAirTerminal)Set to true if system uses CHW
Booleanhave_souHeaWat (from PartialAirTerminal)Set to true if system uses HHW
Nominal condition
Modelica.Units.SI.MassFlowRatemAir_flow_nominal (from PartialAirTerminal)dat.mAir_flow_nominalDischarge air mass flow rate
Modelica.Units.SI.MassFlowRatemAirPri_flow_nominal (from PartialAirTerminal)Primary air mass flow rate
Modelica.Units.SI.MassFlowRatemChiWat_flow_nominal (from PartialAirTerminal)Total CHW mass flow rate
Modelica.Units.SI.MassFlowRatemHeaWat_flow_nominal (from PartialAirTerminal)Total HHW mass flow rate
Modelica.Units.SI.HeatFlowRateQChiWat_flow_nominal (from PartialAirTerminal)Total CHW heat flow rate
Modelica.Units.SI.HeatFlowRateQHeaWat_flow_nominal (from PartialAirTerminal)Total HHW heat flow rate
Dynamics › Conservation equations
Modelica.Fluid.Types.DynamicsenergyDynamics (from PartialAirTerminal)Modelica.Fluid.Types.Dynamics.DynamicFreeInitialType of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalAir (from PartialAirTerminal)true= true to allow flow reversal, false restricts to design direction - Air side
BooleanallowFlowReversalLiq (from PartialAirTerminal)true= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced › Diagnostics
Booleanshow_T (from PartialAirTerminal)false= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDefaultDescription
Modelica.Fluid.Interfaces.FluidPort_aport_Sup (from PartialAirTerminal)Supply air from AHU
Modelica.Fluid.Interfaces.FluidPort_aport_SupCol (from PartialAirTerminal)Dual duct cold deck air supply from AHU
Modelica.Fluid.Interfaces.FluidPort_aport_SupHot (from PartialAirTerminal)Dual duct hot deck air supply from AHU
Modelica.Fluid.Interfaces.FluidPort_bport_Dis (from PartialAirTerminal)Discharge air
Modelica.Fluid.Interfaces.FluidPort_aport_Ret (from PartialAirTerminal)Return air
Modelica.Fluid.Interfaces.FluidPort_aport_aHeaWat (from PartialAirTerminal)HHW supply port
Modelica.Fluid.Interfaces.FluidPort_bport_bHeaWat (from PartialAirTerminal)HHW return port
Buildings.Templates.ZoneEquipment.Interfaces.Busbus (from PartialAirTerminal)Terminal unit control bus

Components

TypeNameDefaultDescription
Buildings.Templates.Components.Coils.WaterBasedHeatingcoiHea (from VAVBox)
Buildings.Templates.Components.Actuators.DamperdamVAV (from VAVBox)VAV damper
Buildings.Templates.ZoneEquipment.Components.Controls.OpenLoopctl (from VAVBox)
Buildings.Templates.Components.Sensors.TemperatureTAirDis (from VAVBox)Discharge air temperature sensor
Buildings.Templates.Components.Sensors.VolumeFlowRateVAirDis_flow (from VAVBox)Airflow sensor

Revisions

  • February 11, 2022, by Antoine Gautier:
    First implementation.