blockBASControlPoints
Emulation of control points from the BAS
Extends from Modelica.Blocks.Icons.Block (Basic graphical layout of input/output block).
Information
This class generates signals typically provided by the BAS. It is aimed for validation purposes only.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Integer | nZon | 2 | Number of served zones |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Interfaces.Bus[nZon] | busTer | Terminal unit control bus |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Controls.OBC.CDL.Logical.Sources.Constant[nZon] | y1OccSch | Scheduled occupancy | |
| Controls.OBC.CDL.Integers.Sources.Constant[nZon] | yOveFloSet | Override flow setpoint, 1: set to zero; 2: set to cooling maximum; 3: set to minimum; 4: set to heating maximum | |
| Controls.OBC.CDL.Logical.Sources.Constant[nZon] | y1OveHeaOff | Override heating coil valve position, true: close valve | |
| Controls.OBC.CDL.Integers.Sources.Constant[nZon] | yOveDamPos | Override damper position, 1: set to close; 2: set to open | |
| Controls.OBC.CDL.Reals.Sources.Constant[nZon] | TZonHeaOccSet | Occupied heating setpoint | |
| Controls.OBC.CDL.Reals.Sources.Constant[nZon] | TZonCooOccSet | Occupied cooling setpoint | |
| Controls.OBC.CDL.Reals.Sources.Constant[nZon] | TZonHeaUnoSet | Unoccupied heating setpoint | |
| Controls.OBC.CDL.Reals.Sources.Constant[nZon] | TZonCooUnoSet | Unoccupied cooling setpoint | |
| Controls.OBC.CDL.Reals.Sources.Constant[nZon] | ppmCO2Set | Zone CO2 concentration setpoint |