modelTestCase10

VDI 6007 Test Case 10 model

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

Test Case 10 of the VDI 6007 Part 1: Calculation of indoor air temperature excited by a radiative and convective heat source for room version S. It is based on Test Case 5, but with a non-adiabatic floor plate to an adjacent room with a fixed temperature.

Boundary conditions

  • daily profile for outdoor air temperature in hourly steps
  • no solar or short-wave radiation on the exterior wall
  • daily profile for solar radiation through the windows in hourly steps
  • sunblind closes at >100 W/m2
  • no long-wave radiation exchange between exterior wall, windows and ambient environment

This test validates linking to ajdacent rooms with fixed temperature.

Components

TypeNameDefaultDescription
RC.TwoElementsthermalZoneTwoElements
Buildings.HeatTransfer.Sources.PrescribedTemperaturepreTemOutdoor air temperature
Modelica.Blocks.Sources.CombiTimeTableintGaiTable with internal gains
Modelica.Blocks.Sources.CombiTimeTablereferenceReference results
Modelica.Thermal.HeatTransfer.Sources.PrescribedHeatFlowmacConvConvective heat flow machines
Modelica.Thermal.HeatTransfer.Sources.PrescribedHeatFlowperRadRadiative heat flow persons
Modelica.Thermal.HeatTransfer.Sources.PrescribedHeatFlowperConConvective heat flow persons
Modelica.Blocks.Sources.CombiTimeTabletableSolRadWindowSolar radiation
Modelica.Blocks.Sources.Constantg_sunblindg value for sunblind closed
Modelica.Blocks.Sources.Constantsunblind_openg value for sunblind open
Modelica.Blocks.Logical.GreaterThresholdgreaterThreshold1Threshold for sunblind for one direction
Modelica.Blocks.Math.Productproduct1Solar radiation times g value for sunblind (open or closed) for one direction
Modelica.Blocks.Logical.Switchswitch1Determines g value for sunblind (open or closed) for one direction
Modelica.Blocks.Sources.CombiTimeTableoutdoorTempOutdoor air temperature
EquivalentAirTemperature.VDI6007eqAirTempEquivalent air temperature
Modelica.Blocks.Sources.ConstantconstDummy black body sky temperature
Modelica.Blocks.Sources.ConstantHSolSolar radiation on walls
Modelica.Blocks.Sources.ConstantsunblindDummy for g value of sunblinds (open)
Modelica.Thermal.HeatTransfer.Components.ConvectiontheConWallOutdoor convective heat transfer
Modelica.Blocks.Sources.ConstanthConWallOutdoor coefficient of heat transfer for walls
BaseClasses.VerifyDifferenceThreePeriodsassEquChecks validation criteria
Modelica.Blocks.Math.MeanmeanHourly mean of indoor air temperature

Revisions

  • July 11, 2019, by Katharina Brinkmann:
    Renamed alphaWall to hConWall
  • July 7, 2016, by Moritz Lauster:
    Added automatic check against validation thresholds.
  • January 11, 2016, by Moritz Lauster:
    Implemented.