modelDispatcher

Ideal fuel dispatcher

Parameters

TypeNameDefaultDescription
ClaRa.Basics.Units.PowerP_elElectric power
Realeta_elPlant efficiency
ClaRa.Basics.Units.MassFlowRatem_flow_fuelP_el/(eta_el*LHV)/N_burner_levelsFuel mass flow (per burner level)
ClaRa.Basics.Units.MassFlowRatem_flow_paPi_m_flows*m_flow_fuelRprt: Primary air mass flow (per burner level)
ClaRa.Basics.Units.MassFlowRatem_flow_fg_total(m_flow_fuel + m_flow_pa)*N_burner_levelsTotal flue gass implied by all mills
RealPi_m_flowslambda*(n_flow_C_primary + n_flow_H_primary/4.0 + n_flow_S_primary - n_flow_O_primary/2)*ClaRa.Basics.Constants.M_O*2.0/max(1e-32, xi_pa_in[6])/m_flow_fuel
Part Load Definition
RealP_target_Target power in p.u.
Real[:,2]CharLine_P_el_[0, 1; 1, 1]Characteristic line of P_el as function of P_target_
Real[:,2]CharLine_eta_el_[0, 1; 1, 1]Characteristic line of eta_el as function of P_target_
Fundamental Definitions
ClaRa.Basics.Media.Fuel.PartialFuelfuelTypesimCenter.fuelModel1Coal elemental composition used for combustion
ClaRa.Basics.Units.EnthalpyMassSpecificLHVNominal lower heating value
ClaRa.Basics.Units.MassFraction[fuelType.nc - 1]xi_fuelfuelType.defaultCompositionFuel composition
IntegerN_burner_levelsNumber of burner levels
Combustion Air
TILMedia.Gas.Types.BaseGasflueGassimCenter.flueGasModelFlue gas model used in component
ClaRa.Basics.Units.MassFraction[flueGas.nc - 1]xi_pa_in{0, 0, 0, 0, 0.77, 0.23, 0, 0, 0}Primary air inlet composition
Reallambda1.15Excess air
Nominal Operation Point
ClaRa.Basics.Units.PowerP_el_nomNominal electric power
Realeta_el_nomNominal plant efficiency

Connectors

TypeNameDefaultDescription
FuelSignal_black_b[N_burner_levels]fuelSignal_black

Components

TypeNameDefaultDescription
ClaRa.SimCentersimCenter