modelVirtualImpedance
Virtual impedance model for the current limitation of grid forming converters
Parameters
| Type | Name | Default | Description |
| Types.PerUnit | KpVI | | Proportional gain of the virtual impedance |
| Types.PerUnit | XRratio | | X/R ratio of the virtual impedance |
| Types.CurrentModulePu | IMaxVI | | Maximum current before activating the virtual impedance in pu (base UNom, SNom) |
| Types.PerUnit | IdConv0Pu | | Start value of d-axis current in the converter in pu (base UNom, SNom) (generator convention) |
| Types.PerUnit | IqConv0Pu | | Start value of q-axis current in the converter in pu (base UNom, SNom) (generator convention) |
| Types.CurrentModulePu | IConvSquare0Pu | | Start value of square current in the converter in pu (base UNom, SNom) |
| Types.CurrentModulePu | DeltaIConvSquare0Pu | | Start value of extra square current in the converter in pu (base UNom, SNom) |
| Types.PerUnit | RVI0 | | Start value of virtual resistance in pu (base UNom, SNom) |
| Types.PerUnit | XVI0 | | Start value of virtual reactance in pu (base UNom, SNom) |
| Types.PerUnit | DeltaVVId0 | | Start value of d-axis virtual impedance output in pu (base UNom) |
| Types.PerUnit | DeltaVVIq0 | | Start value of q-axis virtual impedance output in pu (base UNom) |