modelEpriGFM_INIT

Initialization model for EpriGFM

Extends from AdditionalIcons.Init, Parameters.OmegaFlag (OmegaFlag parameter).

Parameters

TypeNameDefaultDescription
General
IntegerOmegaFlag (from OmegaFlag)GFM control type; 0=GFL, 1=droop, 2=VSM, 3=dVOC
Types.ApparentPowerModuleSNomNominal apparent power in MVA
Circuit
Types.PerUnitRSourcePuResistance in pu (base SNom, UNom), example value = 0.0015
Types.PerUnitXSourcePuReactance in pu (base SNom, UNom), example value = 0.15
Initial
Types.ActivePowerPuP0PuStart value of the active power at the converter's terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0PuStart value of the reactive power at the converter's terminal in pu (base SnRef) (receptor convention)
Types.AngleTheta0Start value of phase shift between the converter's rotating frame and the grid rotating frame in rad
Types.PerUnitU0PuStart value of voltage magnitude at regulated bus in pu (base UNom)

Components

TypeNameDefaultDescription
Types.ComplexCurrentPui0PuStart value of complex current at converter's terminal in pu (base UNom, SnRef) (receptor convention)
Types.PerUnitIdConv0PuStart value of d-axis current of the converter in pu (base UNom, SNom) (generator convention)
Types.PerUnitIqConv0PuStart value of q-axis current of the converter in pu (base UNom, SNom) (generator convention)
Types.ComplexPerUnits0PuStart value of complex apparent power at terminal in pu (base SnRef) (receptor convention)
Types.ComplexVoltagePuu0PuStart value of complex voltage at converter's terminal in pu (base UNom)
Types.PerUnitUdConv0PuStart value of d-axis modulation voltage in pu (base UNom)
Types.PerUnitUdFilter0PuStart value of d-axis voltage at the converter's terminal in pu (base UNom)
Types.PerUnitUqConv0PuStart value of q-axis modulation voltage in pu (base UNom)
Types.PerUnitUqFilter0PuStart value of q-axis voltage at the converter's terminal in pu (base UNom)