modelPowerTransferHVDCEmulation

Power transfer model for HVDC with AC emulation

Extends from Dynawo.Electrical.Controls.HVDC.PowerTransferHVDC (Power transfer model for HVDC).

Information

This model adapts the KACEmulation and PRefSetPu of each of the two HVDC links in parallel depending on the running state of each of the links. If one link is disconnected, this allows the other one to compensate for the power loss.

Parameters

TypeNameDefaultDescription
Types.ActivePowerPuPRefSet10Pu (from PowerTransferHVDC)Start value of reference active power in pu (base SnRef) for HVDC link 1
Types.ActivePowerPuPRefSet20Pu (from PowerTransferHVDC)Start value of reference active power in pu (base SnRef) for HVDC link 2
Types.PerUnitKACEmulation10Start value of inverse of the emulated AC reactance for HVDC link 1
Types.PerUnitKACEmulation20Start value of inverse of the emulated AC reactance for HVDC link 2

Components

TypeNameDefaultDescription
Types.ActivePowerPuPRefSet1RawPu (from PowerTransferHVDC)Raw reference active power of HVDC link 1 in pu (base SnRef)
Types.ActivePowerPuPRefSet2RawPu (from PowerTransferHVDC)Raw reference active power of HVDC link 2 in pu (base SnRef)
Booleanrunning1 (from PowerTransferHVDC)Boolean assessing if the HVDC link 1 is running
Booleanrunning2 (from PowerTransferHVDC)Boolean assessing if the HVDC link 2 is running
Types.ActivePowerPuPRefSet1Pu (from PowerTransferHVDC)Reference active power of HVDC link 1 in pu (base SnRef)
Types.ActivePowerPuPRefSet2Pu (from PowerTransferHVDC)Reference active power of HVDC link 2 in pu (base SnRef)
Types.PerUnitKACEmulation1Inverse of the emulated AC reactance for HVDC link 1
Types.PerUnitKACEmulation2Inverse of the emulated AC reactance for HVDC link 2