modelWPPControl2015

Control model for IEC N°61400-27-1:2015 standard WPP

Extends from Dynawo.Electrical.Controls.IEC.IEC61400.BaseClasses.BaseWPPControl (Base control model for IEC N°61400-27-1 standard WPP), Dynawo.Electrical.Controls.IEC.IEC61400.Parameters.QControlParameters2015.

Parameters

TypeNameDefaultDescription
Types.ApparentPowerModuleSNom (from BaseWPPControl)Nominal converter apparent power in MVA
Types.TimetS (from BaseWPPControl)Integration time step in s
PControlTables
RealTablePwpBiasfwpFiltCom11 (from PControlParameters)0.95
RealTablePwpBiasfwpFiltCom12 (from PControlParameters)1
RealTablePwpBiasfwpFiltCom21 (from PControlParameters)1
RealTablePwpBiasfwpFiltCom22 (from PControlParameters)0
RealTablePwpBiasfwpFiltCom31 (from PControlParameters)1.05
RealTablePwpBiasfwpFiltCom32 (from PControlParameters)-1
RealTablePwpBiasfwpFiltCom41 (from PControlParameters)1.06
RealTablePwpBiasfwpFiltCom42 (from PControlParameters)-1
RealTablePwpBiasfwpFiltCom51 (from PControlParameters)1.07
RealTablePwpBiasfwpFiltCom52 (from PControlParameters)-1
RealTablePwpBiasfwpFiltCom61 (from PControlParameters)1.08
RealTablePwpBiasfwpFiltCom62 (from PControlParameters)-1
RealTablePwpBiasfwpFiltCom71 (from PControlParameters)1.09
RealTablePwpBiasfwpFiltCom72 (from PControlParameters)-1
Real[:,:]TablePwpBiasfwpFiltCom (from PControlParameters)[TablePwpBiasfwpFiltCom11, TablePwpBiasfwpFiltCom12; TablePwpBiasfwpFiltCom21, TablePwpBiasfwpFiltCom22; TablePwpBiasfwpFiltCom31, TablePwpBiasfwpFiltCom32; TablePwpBiasfwpFiltCom41, TablePwpBiasfwpFiltCom42; TablePwpBiasfwpFiltCom51, TablePwpBiasfwpFiltCom52; TablePwpBiasfwpFiltCom61, TablePwpBiasfwpFiltCom62; TablePwpBiasfwpFiltCom71, TablePwpBiasfwpFiltCom72]Table for defining power variation versus frequency
PControlWP
Types.PerUnitDPRefMaxPu (from BaseWPPControl)Maximum positive ramp rate for PD power reference in pu/s (base SNom)
Types.PerUnitDPRefMinPu (from BaseWPPControl)Minimum negative ramp rate for PD power reference in pu/s (base SNom)
Types.PerUnitDPwpRefMaxPu (from BaseWPPControl)Maximum positive ramp rate for WP power reference in pu/s (base SNom)
Types.PerUnitDPwpRefMinPu (from BaseWPPControl)Minimum negative ramp rate for WP power reference in pu/s (base SNom)
Types.PerUnitKiwpp (from BaseWPPControl)Power PI controller integration gain in pu/s (base SNom)
Types.PerUnitKpwpp (from BaseWPPControl)Power PI controller proportional gain in pu (base SNom)
Types.PerUnitKwppRef (from BaseWPPControl)Power reference gain in pu (base SNom)
Types.ActivePowerPuPKiwppMaxPu (from BaseWPPControl)Maximum active power reference from integration in pu (base SNom)
Types.ActivePowerPuPKiwppMinPu (from BaseWPPControl)Minimum active power reference from integration in pu (base SNom)
Types.ActivePowerPuPRefMaxPu (from BaseWPPControl)Maximum PD power reference in pu (base SNom)
Types.ActivePowerPuPRefMinPu (from BaseWPPControl)Minimum PD power reference in pu (base SNom)
Types.TimetpftLead time constant in the reference value transfer function in s
Types.TimetpfvLag time constant in the reference value transfer function in s
Types.TimetWPfFiltPFilter time constant for frequency measurement in s
Types.TimetWPPFiltPFilter time constant for active power measurement in s
QControlWP
Types.PerUnitDXRefMaxPu (from BaseWPPControl)Maximum positive ramp rate for WT reactive power or voltage reference in pu/s (base SNom or UNom) (generator convention)
Types.PerUnitDXRefMinPu (from BaseWPPControl)Minimum negative ramp rate for WT reactive power or voltage reference in pu/s (base SNom or UNom) (generator convention)
Types.PerUnitKiwpx (from BaseWPPControl)Reactive power or voltage PI controller integral gain in pu/s (base SNom)
Types.PerUnitKpwpx (from BaseWPPControl)Reactive power or voltage PI controller proportional gain in pu (base SNom)
Types.PerUnitKwpqRef (from BaseWPPControl)Reactive power reference gain in pu (base SNom)
Types.PerUnitKwpqu (from BaseWPPControl)Voltage controller cross coupling gain in pu (base SNom)
IntegerMwpqMode (from BaseWPPControl)Control mode (0 : reactive power reference, 1 : power factor reference, 2 : UQ static, 3 : voltage control)
Types.TimetUqFilt (from BaseWPPControl)Time constant for the UQ static mode in s
Types.VoltageModulePuUwpqDipPu (from BaseWPPControl)Voltage threshold for UVRT detection in pu (base UNom)
Types.PerUnitXKiwpxMaxPu (from BaseWPPControl)Maximum WT reactive power or voltage reference from integration in pu (base SNom or UNom) (generator convention)
Types.PerUnitXKiwpxMinPu (from BaseWPPControl)Minimum WT reactive power or voltage reference from integration in pu (base SNom or UNom) (generator convention)
Types.PerUnitXRefMaxPu (from BaseWPPControl)Maximum WT reactive power or voltage reference in pu (base SNom or UNom) (generator convention)
Types.PerUnitXRefMinPu (from BaseWPPControl)Minimum WT reactive power or voltage reference in pu (base SNom or UNom) (generator convention)
Types.TimetWPPFiltQFilter time constant for active power measurement in s
Types.TimetWPQFiltQFilter time constant for reactive power measurement in s
Types.TimetWPUFiltQFilter time constant for voltage measurement in s
Types.TimetxftLead time constant in the reference value transfer function in s
Types.TimetxfvLag time constant in the reference value transfer function in s
Initialization
Types.ComplexCurrentPui0Pu (from BaseWPPControl)Initial complex current at grid terminal in pu (base UNom, SnRef) (receptor convention)
Types.ComplexVoltagePuu0Pu (from BaseWPPControl)Initial complex voltage at grid terminal in pu (base UNom)
Operating point
Types.ActivePowerPuP0Pu (from BaseWPPControl)Initial active power at grid terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0Pu (from BaseWPPControl)Initial reactive power at grid terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from BaseWPPControl)Initial voltage amplitude at grid terminal in pu (base UNom)
Types.AngleUPhase0 (from BaseWPPControl)Initial voltage angle at grid terminal in rad
Types.PerUnitX0Pu (from BaseWPPControl)Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention)
Types.PerUnitXWT0Pu (from BaseWPPControl)Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention)
QControlTables
RealTableQwpUErr11 (from QControlParameters2015)-0.05
RealTableQwpUErr12 (from QControlParameters2015)1.21
RealTableQwpUErr21 (from QControlParameters2015)0
RealTableQwpUErr22 (from QControlParameters2015)0.21
RealTableQwpUErr31 (from QControlParameters2015)0.05
RealTableQwpUErr32 (from QControlParameters2015)-0.79
RealTableQwpUErr41 (from QControlParameters2015)0.06
RealTableQwpUErr42 (from QControlParameters2015)-0.79
RealTableQwpUErr51 (from QControlParameters2015)0.07
RealTableQwpUErr52 (from QControlParameters2015)-0.79
RealTableQwpUErr61 (from QControlParameters2015)0.08
RealTableQwpUErr62 (from QControlParameters2015)-0.79
Real[:,:]TableQwpUErr (from QControlParameters2015)[TableQwpUErr11, TableQwpUErr12; TableQwpUErr21, TableQwpUErr22; TableQwpUErr31, TableQwpUErr32; TableQwpUErr41, TableQwpUErr42; TableQwpUErr51, TableQwpUErr52; TableQwpUErr61, TableQwpUErr62]Table for the UQ static mode

Connectors

TypeNameDefaultDescription
Modelica.ComplexBlocks.Interfaces.ComplexInputiPu (from BaseWPPControl)Complex current at grid terminal in pu (base UNom, SNom) (generator convention)
Modelica.Blocks.Interfaces.RealInputomegaRefPu (from BaseWPPControl)Grid angular frequency in pu (base omegaNom)
Modelica.Blocks.Interfaces.RealInputPWPRefPu (from BaseWPPControl)Reference active power in pu (base SNom) (generator convention)
Modelica.ComplexBlocks.Interfaces.ComplexInputuPu (from BaseWPPControl)Complex voltage at grid terminal in pu (base UNom)
Modelica.Blocks.Interfaces.RealOutputy (from BaseWPPControl)
Modelica.Blocks.Interfaces.RealInputQWPRefPuReference reactive power in pu (base SNom) (generator convention)
Modelica.Blocks.Interfaces.RealInputtanPhiTangent phi (can be figured as QPu / PPu)
Modelica.Blocks.Interfaces.RealInputUWPRefPuReference voltage in pu (base UNom) (generator convention)
Modelica.Blocks.Interfaces.RealOutputPWTRefPuReference active power communicated to WT in pu (base SNom) (generator convention)
Modelica.Blocks.Interfaces.RealOutputxWTRefPuReference reactive power or voltage communicated to WT in pu (base SNom or UNom) (generator convention)

Components

TypeNameDefaultDescription
Dynawo.Electrical.Controls.IEC.IEC61400.BaseControls.WPP.WPPPControl2015pControl
Dynawo.Electrical.Controls.IEC.IEC61400.BaseControls.WPP.WPPQControl2015qControl
Modelica.ComplexBlocks.ComplexMath.Productproduct
Modelica.ComplexBlocks.ComplexMath.ComplexToRealcomplexToReal