| Types.ActivePowerPu | PGen0Pu | | Initial value of generated active electrical power in pu (base SystemBase.SnRef) (generator convention) (use PGen0Pu of the generator system or Pm0Pu*PBaseMw/PGenBaseMw) |
| Types.ActivePowerPu | Pm0Pu | | Initial value of mechanical power in pu (base PNomTurb) (generator convention) |
| Types.ActivePowerPu | PRef0Pu | PGen0Pu*PGenBaseMw/PBaseMw | |
| Valves |
| Types.PerUnit | CHcPu | | Control valves rate closing limit in pu/s (base PNomTurb), typical value = -3.3 |
| Types.PerUnit | CHoPu | | Control valves rate opening limit in pu/s (base PNomTurb), typical value = 0.17 |
| Types.PerUnit | CIcPu | | Intercept valves rate closing limit in pu/s (base PNomTurb), typical value = -2.2 |
| Types.PerUnit | CIoPu | | Intercept valves rate opening limit in pu/s (base PNomTurb), typical value = 0.123 |
| Types.PerUnit | HHpMaxPu | | Maximum control valve position in pu (base PNomTurb), typical value = 1 |
| Types.Time | tVHp | | Control valves servo time constant in s, typical value = 0.1 |
| Types.Time | tVLp | | Intercept valves servo time constant in s, typical value = 0.15 |
| Grid connected control |
| Types.PerUnit | DeltafDbPu | | Deadband of the frequency corrector in pu (base fNom), typical value = 0 |
| Types.PerUnit | KE | | Governor controller proportional gain, typical value = 0.65 |
| Types.PerUnit | KFCor | | Frequency corrector gain, typical value = 20 |
| Types.AngularVelocityPu | OmegaFMaxPu | | Upper limit for frequency correction in pu (base SystemBase.omegaNom), typical value = 0.05 |
| Types.AngularVelocityPu | OmegaFMinPu | | Lower limit for frequency correction in pu (base SystemBase.omegaNom), typical value = -0.05 |
| Types.ActivePowerPu | PMaxPu | | Maximal active power of the turbine in pu (base PNomTurb), typical value = 1 |
| Types.Time | tDp | | Power controller derivative time constant in s, typical value = 1e-9 |
| Types.Time | tEn | | Electro hydraulic transducer time constant in s, typical value = 0.1 |
| Types.Time | tF | | Frequency transducer time constant in s, typical value = 1e-9 |
| Types.Time | tFp | | Power controller derivative numerical approximation time constant in s, typical value = 1e-9 |
| Types.Time | tIp | | Power controller integral time constant in s, typical value = 2 |
| Types.Time | tP | | Power transducer time constant in s, typical value = 0.07 |
| Islanded control |
| Types.AngularVelocityPu | DeltaOmegaDbPu | | Deadband of the speed governor in pu (base SystemBase.omegaNom), typical value = 0.0004 |
| Types.PerUnit | KOmegaCor | | Speed governor gain, typical value = 20 |
| Types.AngularVelocityPu | OmegaOmegaMaxPu | | Upper limit for the speed governor frequency correction in pu (base SystemBase.omegaNom), typical value = 0.1 |
| Types.AngularVelocityPu | OmegaOmegaMinPu | | Lower limit for the speed governor frequency correction in pu (base SystemBase.omegaNom), typical value = -1 |
| Types.Time | tOmega | | Speed transducer time constant in s, typical value = 0.02 |
| Turbine / boiler |
| Types.PerUnit | KHp | | Turbine output gain for HP part, typical value = 0.277 |
| Types.PerUnit | KLp | | Turbine output gain for LP part, typical value = 0.723 |
| Types.PerUnit | PRhMaxPu | | Maximum low pressure limit in pu (base PNomTurb), typical value = 1.4 |
| Types.Time | tB | | Boiler time constant in s, typical value = 100 |
| Types.Time | tHp | | High pressure turbine time constant in s, typical value = 0.31 |
| Types.Time | tLp | | Low pressure turbine time constant in s, typical value = 0.45 |
| Types.Time | tRh | | Reheater time constant in s, typical value = 8 |
| Emergency control |
| Types.AngularVelocityPu | OmegaMax1Pu | | Emergency speed control lower limit in pu (base SystemBase.omegaNom), typical value = 1.025 |
| Types.AngularVelocityPu | OmegaMax2Pu | | Emergency speed control upper limit in pu (base SystemBase.omegaNom), typical value = 1.05 |
| Types.PerUnit | SimxPu | | Intercept valves transfer limit in pu (base PNomTurb), typical value = 0.425 |
| General |
| Types.ActivePowerPu | PBaseMw | | Base power of the machine in [MW, MVA], typical value = PNomTurb |
| Types.ActivePowerPu | PGenBaseMw | SystemBase.SnRef | Base power for measured electrical power in [MW, MVA], typical value = SystemBase.SnRef |