modelVRProportional

Simple proportional voltage regulator

Parameters

TypeNameDefaultDescription
Types.VoltageModulePuEfdMaxPuMaximum allowed exciter field voltage in pu (user-selected base voltage)
Types.VoltageModulePuEfdMinPuMinimum allowed exciter field voltage in pu (user-selected base voltage)
Types.PerUnitGainControl gain
Types.TimeLagEfdMaxTime lag before taking action when going above EfdMax in s
Types.TimeLagEfdMinTime lag before taking action when going below EfdMin in s
Types.VoltageModulePuUsRefMaxPuMaximum reference stator voltage in pu (base UNom)
Types.VoltageModulePuUsRefMinPuMinimum reference stator voltage in pu (base UNom)
Types.VoltageModulePuEfd0PuInitial exciter field voltage, i.e. Efd0PuLF if compliant with saturations, in pu (user-selected base voltage)
Types.VoltageModulePuEfd0PuLFInitial exciter field voltage from LoadFlow in pu (user-selected base voltage)
Types.VoltageModulePuUs0PuInitial stator voltage in pu (base UNom)
Types.VoltageModulePuUsRef0PuInitial reference stator voltage in pu (base UNom)

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputdeltaUsRefPuAdditional reference stator voltage in pu (base UNom)
Modelica.Blocks.Interfaces.RealInputUsPuStator voltage in pu (base UNom)
Modelica.Blocks.Interfaces.RealInputUsRefPuReference stator voltage in pu (base UNom)
Modelica.Blocks.Interfaces.RealOutputEfdPuExciter field voltage in pu (user-selected base voltage)
Dynawo.Connectors.BPinlimitationDownIf true, lower limit is reached
Dynawo.Connectors.BPinlimitationUpIf true, upper limit is reached

Components

TypeNameDefaultDescription
Dynawo.NonElectrical.Blocks.NonLinear.LimiterWithLaglimiterWithLagLimiter activated only after a given period outside the bounds
Modelica.Blocks.Math.Gaingain
Modelica.Blocks.Math.Feedbackfeedback
Modelica.Blocks.Nonlinear.LimiterlimUsRef
Modelica.Blocks.Math.AddUsRefTotal