modelLVRTDERa
Low-voltage ride-through model for the der_a
Parameters
| Type | Name | Default | Description |
| Types.VoltageModulePu | Ul0Pu | | Voltage threshold under which all inverters are disconnected in pu (base UNom) |
| Types.VoltageModulePu | Ul1Pu | | Voltage threshold under which inverters start to disconnect in pu (base UNom) |
| Types.Time | tvl0 | | Time after which inverters stay definitively disconnected if V < Ul0Pu in s |
| Types.Time | tvl1 | | Time after which non-recovering inverters stay disconnected if V < Ul1Pu in s |
| Real | RecoveringShare | | Share of inverters that reconnect when V > Ul1Pu |
Components
| Type | Name | Default | Description |
| Types.VoltageModulePu | UMinPu | | Voltage when V has been lower than Ul0Pu for tvl0 seconds in pu (base UNom) |
| Types.Time | tUl0Reached | | Time when UMonitoredPu dropped below Ul0Pu in s |
| Types.Time | tUl1Reached | | Time when UMonitoredPu dropped below Ul1Pu in s |
| Boolean | Ul0Reached | | True if UMonitoredPu stayed below Ul0Pu for tvl0 |
| Boolean | Ul1Reached | | True if UMonitoredPu stayed below Ul1Pu for tvl1 |