modelOVRTDERa

Over-voltage ride-through model for the der_a

Parameters

TypeNameDefaultDescription
Types.VoltageModulePuUh0PuVoltage threshold over which all inverters are disconnected in pu (base UNom)
Types.VoltageModulePuUh1PuVoltage threshold over which inverters start to disconnect in pu (base UNom)
Types.Timetvh0Time after which inverters stay definitively disconnected if V > Uh0Pu in s
Types.Timetvh1Time after which non-recovering inverters stay disconnected if V > Uh1Pu in s
RealRecoveringShareShare of inverters that reconnect when V < Uh1Pu

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputUMonitoredPuMonitored voltage in pu (base UNom)
Modelica.Blocks.Interfaces.RealOutputconnectedShareConnected share

Components

TypeNameDefaultDescription
Types.VoltageModulePuUMaxPuVoltage when V has been higher than Uh0Pu for tvh0 seconds in pu (base UNom)
Types.TimetUh0ReachedTime when UMonitoredPu rised above Uh0Pu in s
Types.TimetUh1ReachedTime when UMonitoredPu rised above Uh1Pu in s
BooleanUh0ReachedTrue if UMonitoredPu stayed above Uh0Pu for tvh0
BooleanUh1ReachedTrue if UMonitoredPu stayed above Uh1Pu for tvh1