modelBaseDistanceProtectionLine

Base model for line distance protection

Parameters

TypeNameDefaultDescription
IntegerNbZonesNumber of zones in the distance protection scheme
IntegerLineSideSide of the line where the distance protection is located
Types.TimetZoneTime delay for trips in zone i in s (for each protected zone)
Types.PerUnitRPuResistive reach of zone i in pu (base UNom, SnRef) (for each protected zone)
Types.PerUnitXPuReactive reach of zone i in pu (base UNom, SnRef) (for each protected zone)
BooleanTrippingZoneTrue if zone i can send a tripping signal
Types.TimeCircuitBreakerTimeTime required to open the circuit breaker in s
BooleanWithBlinderTrue if a load blinder is used
Types.AngleBlinderAnglePuLoad angle of the load blinder in rad
RealBlinderReachPuReach in the Z plane of the load blinder in pu (base UNom, SnRef)

Connectors

TypeNameDefaultDescription
Connectors.IntPinlineStateSwitch off message for the protected line

Components

TypeNameDefaultDescription
Types.VoltageModulePuUMonitoredPuMonitored voltage in pu (base UNom)
Types.ActivePowerPuPMonitoredPuMonitored active power in pu (base SnRef)
Types.ReactivePowerPuQMonitoredPuMonitored reactive power in pu (base SnRef)
BooleanBlindedTrue if the apparent impedance is in the load blinder area
Booleantrippedtrue if the protection tripped (for each protected zone)
Types.TimetThresholdReachedTime when the apparent impedance enters zone i in s (for each protected zone)