modelLackOfVoltageRelay

Information

This lack of voltage relay triggers the opening or closing of its controlled switch in lack of voltage situations or restorations thereof. 

When the voltages of a bus and a directly connected equipment (e.g. a line) fall under a certain threshold, the relay opens the corresponding switch.

The relay closes its switch depending on the chosen mode. When the RecloserModeInput is set to
  • Equipment Recloser Mode, the relay checks whether a sufficient voltage is present on the bus side in order to restore voltage on the equipment side.
  • Bus Recloser Mode, the relay checks whether a sufficient voltage is present on the equipment side in order to restore voltage on the bus side.
  • Recoupler Mode, the relay checks if voltages of both bus and equipment are sufficient and they are in reasonable synchronicity (voltage and phase are within a certain range of each other)
The sleep mode is triggered for all relays of a substation when the trip condition of the relay is activated - it represents a time window in which reclose actions of any relay are allowed in order to restore voltage. If the sleep duration is expired, no more reclose can happen from a relay of this type on the substation.

A usage of this relay is demonstrated in the dynawo examples (DynaWaltz/IEEE14/IEEE14_LackOfVoltage).

Parameters

TypeNameDefaultDescription
Types.VoltageModulePuUMonitoredEquipmentTripPu0.2Eq voltage threshold to trigger
Types.VoltageModulePuUMonitoredBusTripPu0.2Bus voltage threshold to trigger bus trip
Types.VoltageModulePuUMonitoredEquipmentMinPu0.8Minimum equipment voltage
Types.VoltageModulePuUMonitoredBusMinPu0.8Minimum bus voltage
Types.VoltageModulePuUMonitoredDeltaMaxPu0.01Maximum allowed voltage difference between bus and equipment
Types.AngleUPhaseMonitoredDeltaMax30Maximum allowed phase angle difference
Types.TimeTripDelay2Trip delay time in seconds
Types.TimeRecloserDelay3Recloser delay time in seconds
Types.TimeSleepDuration10Sleep mode duration in seconds (stand by)
RecloserModeStateRecloserModeInputRecloserModeState.EquipmentRecloserRecloser operation mode input
OpeningEnabledStateOpeningEnabledOpeningEnabledState.EnableCurrent opening enable/disable state
ReclosingEnabledStateReclosingEnabledReclosingEnabledState.EnableCurrent reclosing enable/disable state

Connectors

TypeNameDefaultDescription
Interfaces.RealInputUMonitoredBusPuMonitored bus voltage in pu (base UNom)
Interfaces.RealInputUPhaseMonitoredBusPhase angle of the monitored bus
Interfaces.RealInputUMonitoredEquipmentPuMonitored equipment voltage in pu (base UNom)
Interfaces.RealInputUPhaseMonitoredEquipmentPhase angle of the monitored equipment
Interfaces.IntegerOutputswitchControlSignalSignal that controls the switches state (open = 1, closed = 2)

Contents

NameDescription
OpeningEnabledState
ReclosingEnabledState
SleepModeState
RecloserModeState