modelLackOfVoltageRelay
Information
This lack of voltage relay triggers the opening or closing of its controlled switch in lack of voltage situations or restorations thereof.When the voltages of a bus and a directly connected equipment (e.g. a line) fall under a certain threshold, the relay opens the corresponding switch.
The relay closes its switch depending on the chosen mode. When the RecloserModeInput is set to
- Equipment Recloser Mode, the relay checks whether a sufficient voltage is present on the bus side in order to restore voltage on the equipment side.
- Bus Recloser Mode, the relay checks whether a sufficient voltage is present on the equipment side in order to restore voltage on the bus side.
- Recoupler Mode, the relay checks if voltages of both bus and equipment are sufficient and they are in reasonable synchronicity (voltage and phase are within a certain range of each other)
The sleep mode is triggered for all relays of a substation when the trip condition of the relay is activated - it represents a time window in which reclose actions of any relay are allowed in order to restore voltage. If the sleep duration is expired, no more reclose can happen from a relay of this type on the substation.
A usage of this relay is demonstrated in the dynawo examples (DynaWaltz/IEEE14/IEEE14_LackOfVoltage).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Types.VoltageModulePu | UMonitoredEquipmentTripPu | 0.2 | Eq voltage threshold to trigger |
| Types.VoltageModulePu | UMonitoredBusTripPu | 0.2 | Bus voltage threshold to trigger bus trip |
| Types.VoltageModulePu | UMonitoredEquipmentMinPu | 0.8 | Minimum equipment voltage |
| Types.VoltageModulePu | UMonitoredBusMinPu | 0.8 | Minimum bus voltage |
| Types.VoltageModulePu | UMonitoredDeltaMaxPu | 0.01 | Maximum allowed voltage difference between bus and equipment |
| Types.Angle | UPhaseMonitoredDeltaMax | 30 | Maximum allowed phase angle difference |
| Types.Time | TripDelay | 2 | Trip delay time in seconds |
| Types.Time | RecloserDelay | 3 | Recloser delay time in seconds |
| Types.Time | SleepDuration | 10 | Sleep mode duration in seconds (stand by) |
| RecloserModeState | RecloserModeInput | RecloserModeState.EquipmentRecloser | Recloser operation mode input |
| OpeningEnabledState | OpeningEnabled | OpeningEnabledState.Enable | Current opening enable/disable state |
| ReclosingEnabledState | ReclosingEnabled | ReclosingEnabledState.Enable | Current reclosing enable/disable state |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Interfaces.RealInput | UMonitoredBusPu | Monitored bus voltage in pu (base UNom) | |
| Interfaces.RealInput | UPhaseMonitoredBus | Phase angle of the monitored bus | |
| Interfaces.RealInput | UMonitoredEquipmentPu | Monitored equipment voltage in pu (base UNom) | |
| Interfaces.RealInput | UPhaseMonitoredEquipment | Phase angle of the monitored equipment | |
| Interfaces.IntegerOutput | switchControlSignal | Signal that controls the switches state (open = 1, closed = 2) |
Contents
| Name | Description |
|---|---|
| OpeningEnabledState | |
| ReclosingEnabledState | |
| SleepModeState | |
| RecloserModeState |