modelWECCInverterCurrentSource_INIT
Initialization model for WECC models with a current source as interface with the grid
Extends from AdditionalIcons.Init, Dynawo.Electrical.Controls.WECC.Parameters.ParamsLvTfo.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Types.PerUnit | RPu (from ParamsLvTfo) | if ConverterLVControl then 1e-5 else RLvTrPu | Serial resistance between injector output and LvTfo in pu (base UNom, SNom). Including source resistance for voltage source. |
| Types.PerUnit | XPu (from ParamsLvTfo) | if ConverterLVControl then 1e-5 else XLvTrPu | Serial reactance between injector output and LvTfo in pu (base UNom, SNom). Including source resistance for voltage source. |
| Types.ApparentPowerModule | SNom | Nominal apparent power in MVA | |
| Types.ActivePowerPu | P0Pu | Start value of active power at converter terminal in pu (receptor convention) (base SnRef) | |
| Types.ReactivePowerPu | Q0Pu | Start value of reactive power at converter terminal in pu (receptor convention) (base SnRef) | |
| Types.VoltageModulePu | U0Pu | Start value of voltage magnitude at regulated bus in pu (bae UNom) | |
| Types.Angle | UPhase0 | Start value of voltage phase angle at regulated bus in rad | |
| LV transformer | |||
| Types.PerUnit | RLvTrPu (from ParamsLvTfo) | Serial resistance of LV transformer in pu (base UNom, SNom). Including source resistance for voltage source. | |
| Types.PerUnit | XLvTrPu (from ParamsLvTfo) | Serial reactance of LV transformer in pu (base UNom, SNom). Including source reactance for voltage source. | |
| Boolean | ConverterLVControl (from ParamsLvTfo) | If true, the converter is controlling at its output (LV side of its transformer), if false, after its transformer (MV side) | |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Types.ComplexCurrentPu | i0Pu | Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention) | |
| Types.PerUnit | Id0Pu | Start value of d-axis current at injector in pu (base UNom, SNom) (generator convention) | |
| Types.ComplexPerUnit | iConv0Pu | Start value of complex current at converter terminal in pu (base UNom, SNom) (generator convention) | |
| Types.ComplexPerUnit | iInj0Pu | Start value of complex current at injector in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | Iq0Pu | Start value of q-axis current at injector in pu (base UNom, SNom) (generator convention) | |
| Types.ActivePowerPu | PInj0Pu | Start value of active power at injector in pu (base SNom) (generator convention) | |
| Types.PerUnit | PConv0Pu | Start value of active power at converter terminal in pu (base SNom) (generator convention) | |
| Types.PerUnit | PF0 | Start value of power factor | |
| Types.PerUnit | QInj0Pu | Start value of reactive power at injector in pu (base SNom) (generator convention) | |
| Types.ReactivePowerPu | QConv0Pu | Start value of reactive power at converter terminal in pu (base SNom) (generator convention) | |
| Types.ComplexPerUnit | s0Pu | Start value of complex apparent power at terminal in pu (base SnRef) (receptor convention) | |
| Types.ComplexPerUnit | sConv0Pu | Start value of complex apparent power at converter in pu (base SNom) (generator convention) | |
| Types.ComplexPerUnit | sInj0Pu | Start value of complex apparent power at injector in pu (base SNom) (generator convention) | |
| Types.ComplexVoltagePu | u0Pu | Start value of complex voltage at terminal in pu (base UNom) | |
| Types.VoltageModulePu | UConv0Pu | Start value of voltage module at converter terminal in pu (base UNom) | |
| Types.ComplexPerUnit | uConv0Pu | Start value of complex voltage at converter terminal in pu (base UNom) | |
| Types.VoltageModulePu | UInj0Pu | Start value of voltage module at injector in pu (base UNom) | |
| Types.ComplexPerUnit | uInj0Pu | Start value of complex voltage at injector in pu (base UNom) | |
| Types.Angle | UPhaseConv0 | Value of voltage phase angle at converter terminal in rad |