recordParamsPCS

Extends from Dynawo.Electrical.Controls.WECC.Parameters.ParamsLvTfo.

Parameters

TypeNameDefaultDescription
Types.PerUnitRPu (from ParamsLvTfo)if ConverterLVControl then 1e-5 else RLvTrPuSerial resistance between injector output and LvTfo in pu (base UNom, SNom). Including source resistance for voltage source.
Types.PerUnitXPu (from ParamsLvTfo)if ConverterLVControl then 1e-5 else XLvTrPuSerial reactance between injector output and LvTfo in pu (base UNom, SNom). Including source resistance for voltage source.
Types.ApparentPowerModuleSNomNominal apparent power in MVA
Types.PerUnitBPcsPuif PPCLocal then BMvHvPu else 1e-5Shunt susceptance between converter terminal and model's output terminal in pu (base UNom, SNom)
Types.PerUnitGPcsPuif PPCLocal then GMvHvPu else 1e-5Shunt conductance between converter terminal and model's output terminal in pu (base UNom, SNom)
Types.PerUnitRPcsPuif PPCLocal and ConverterLVControl then RLvTrPu + RMvHvPu elseif PPCLocal and not ConverterLVControl then RMvHvPu elseif not PPCLocal and ConverterLVControl then RLvTrPu else 1e-5Serial resistance between converter terminal and model's output terminal in pu (base UNom, SNom)
Types.PerUnitXPcsPuif PPCLocal and ConverterLVControl then XLvTrPu + XMvHvPu elseif PPCLocal and not ConverterLVControl then XMvHvPu elseif not PPCLocal and ConverterLVControl then XLvTrPu else 1e-5Serial reactance between converter terminal and model's output terminal in pu (base UNom, SNom)
LV transformer
Types.PerUnitRLvTrPu (from ParamsLvTfo)Serial resistance of LV transformer in pu (base UNom, SNom). Including source resistance for voltage source.
Types.PerUnitXLvTrPu (from ParamsLvTfo)Serial reactance of LV transformer in pu (base UNom, SNom). Including source reactance for voltage source.
BooleanConverterLVControl (from ParamsLvTfo)If true, the converter is controlling at its output (LV side of its transformer), if false, after its transformer (MV side)
MV network + MV/HV transformer
Types.PerUnitBMvHvPu0Shunt susceptance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitGMvHvPu0Shunt conductance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitRMvHvPu0Serial resistance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitXMvHvPu0Serial reactance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitrTfoPu1Transformation ratio in pu: UWT_terminal/UWTG_terminal in no load conditions
BooleanPPCLocalIf true, the Power Park Control is controlling at model's output terminal, if false, at a remote terminal using external measurements