recordParamsPCS
Extends from Dynawo.Electrical.Controls.WECC.Parameters.ParamsLvTfo.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Types.PerUnit | RPu (from ParamsLvTfo) | if ConverterLVControl then 1e-5 else RLvTrPu | Serial resistance between injector output and LvTfo in pu (base UNom, SNom). Including source resistance for voltage source. |
| Types.PerUnit | XPu (from ParamsLvTfo) | if ConverterLVControl then 1e-5 else XLvTrPu | Serial reactance between injector output and LvTfo in pu (base UNom, SNom). Including source resistance for voltage source. |
| Types.ApparentPowerModule | SNom | Nominal apparent power in MVA | |
| Types.PerUnit | BPcsPu | if PPCLocal then BMvHvPu else 1e-5 | Shunt susceptance between converter terminal and model's output terminal in pu (base UNom, SNom) |
| Types.PerUnit | GPcsPu | if PPCLocal then GMvHvPu else 1e-5 | Shunt conductance between converter terminal and model's output terminal in pu (base UNom, SNom) |
| Types.PerUnit | RPcsPu | if PPCLocal and ConverterLVControl then RLvTrPu + RMvHvPu elseif PPCLocal and not ConverterLVControl then RMvHvPu elseif not PPCLocal and ConverterLVControl then RLvTrPu else 1e-5 | Serial resistance between converter terminal and model's output terminal in pu (base UNom, SNom) |
| Types.PerUnit | XPcsPu | if PPCLocal and ConverterLVControl then XLvTrPu + XMvHvPu elseif PPCLocal and not ConverterLVControl then XMvHvPu elseif not PPCLocal and ConverterLVControl then XLvTrPu else 1e-5 | Serial reactance between converter terminal and model's output terminal in pu (base UNom, SNom) |
| LV transformer | |||
| Types.PerUnit | RLvTrPu (from ParamsLvTfo) | Serial resistance of LV transformer in pu (base UNom, SNom). Including source resistance for voltage source. | |
| Types.PerUnit | XLvTrPu (from ParamsLvTfo) | Serial reactance of LV transformer in pu (base UNom, SNom). Including source reactance for voltage source. | |
| Boolean | ConverterLVControl (from ParamsLvTfo) | If true, the converter is controlling at its output (LV side of its transformer), if false, after its transformer (MV side) | |
| MV network + MV/HV transformer | |||
| Types.PerUnit | BMvHvPu | 0 | Shunt susceptance of internal MV network + MV/HV transformer in pu (base UNom, SNom) |
| Types.PerUnit | GMvHvPu | 0 | Shunt conductance of internal MV network + MV/HV transformer in pu (base UNom, SNom) |
| Types.PerUnit | RMvHvPu | 0 | Serial resistance of internal MV network + MV/HV transformer in pu (base UNom, SNom) |
| Types.PerUnit | XMvHvPu | 0 | Serial reactance of internal MV network + MV/HV transformer in pu (base UNom, SNom) |
| Types.PerUnit | rTfoPu | 1 | Transformation ratio in pu: UWT_terminal/UWTG_terminal in no load conditions |
| Boolean | PPCLocal | If true, the Power Park Control is controlling at model's output terminal, if false, at a remote terminal using external measurements | |