| Types.CurrentModulePu | Id0Pu | | Start value of d-component current at injector terminal in pu (generator convention) (base SNom, UNom) |
| Types.CurrentModulePu | Iq0Pu | | Start value of q-component current at injector terminal in pu (generator convention) (base SNom, UNom) |
| Types.PerUnit | PF0 | | Start value of powerfactor |
| Types.ActivePowerPu | PInj0Pu | | Start value of active power at injector terminal in pu (generator convention) (base SNom) |
| Types.ReactivePowerPu | QInj0Pu | | Start value of reactive power at injector terminal in pu (generator convention) (base SNom) |
| Types.VoltageModulePu | UInj0Pu | | Start value of voltage magnitude at injector terminal in pu (base UNom) |
| Electrical Control |
| Boolean | PfFlag | | Power factor flag: Q control (0) or pf control(1) |
| Boolean | PQFlag | | Q/P priority: Q priority (0) or P priority (1) |
| Boolean | QFlag | | Q control flag: const. pf or Q ctrl (0) or voltage/Q (1) |
| Boolean | VFlag | | Voltage control flag: voltage control (0) or Q ctrl (1) |
| Types.VoltageModulePu | Dbd1Pu | | Overvoltage deadband for reactive current injection in pu (base UNom) (typical: -0.1..0) |
| Types.VoltageModulePu | Dbd2Pu | | Undervoltage deadband for reactive current injection in pu (base UNom) (typical: 0..0.1) |
| Types.PerUnit | DPMaxPu | | Active power upper rate limit in pu/s (base SNom) (typical: > 0.1, set to 99 to disable) |
| Types.PerUnit | DPMinPu | | Active power lower rate limit in pu/s (base SNom) (typical: < -0.1, set to -99 to disable) |
| Types.CurrentModulePu | IMaxPu | | Maximal apparent current magnitude in pu (base UNom, SNom) (typical: 1..2) |
| Types.PerUnit | Iqh1Pu | | Maximum reactive current injection (typical: 1..1.1) in pu (base UNom, SNom) |
| Types.PerUnit | Iql1Pu | | Minimum reactive current injection (typical: -1.1..-1) in pu (base UNom, SNom) |
| Types.PerUnit | Kqi | | Integrator gain local reactive power PI controller |
| Types.PerUnit | Kqp | | Proportional gain local reactive power PI controller |
| Types.PerUnit | Kqv | | K-Factor, reactive current injection gain (typical: 0..10) |
| Types.PerUnit | Kvi | | Integrator gain local voltage PI controller |
| Types.PerUnit | Kvp | | Proportional gain local voltage PI controller |
| Types.ActivePowerPu | PMaxPu | | Active power upper limit in pu (base SNom) (typical: 1) |
| Types.ActivePowerPu | PMinPu | | Active power lower limit in pu (base SNom) (typical: 0) |
| Types.ReactivePowerPu | QMaxPu | | Reactive power upper limit, when vFlag == 1 in pu (base SNom) |
| Types.ReactivePowerPu | QMinPu | | Reactive power lower limit, when vFlag == 1 in pu (base SNom) |
| Types.Time | tIq | | Filter time constant reactive current in s(typical: 0.01..0.02) |
| Types.Time | tRv | | Filter time constant terminal voltage in s(typical: 0.01..0.02) |
| Types.Time | tP | | Filter time constant active power in s (typical: 0.1..0.2) |
| Types.Time | tPord | | Filter time constant inverter active power in s |
| Types.VoltageModulePu | VDipPu | | Low voltage condition trigger voltage for FRT in pu (base UNom) (typical: 0..0.9) |
| Types.VoltageModulePu | VMaxPu | | Maximum voltage at inverter terminal in pu (base UNom) (typical: 1.05..1.15) |
| Types.VoltageModulePu | VMinPu | | Minimum voltage at inverter terminal in pu (base UNom) (typical: 0.85..0.95) |
| Types.VoltageModulePu | VRef0Pu | | Reference voltage for reactive current injection in pu (base UNom) (typical: 0.95..1.05) |
| Types.VoltageModulePu | VUpPu | | High voltage condition trigger voltage for FRT in pu (base UNom) (typical: 1.1..1.3) |