recordParamsREEC

Parameters

TypeNameDefaultDescription
Types.CurrentModulePuId0PuStart value of d-component current at injector terminal in pu (generator convention) (base SNom, UNom)
Types.CurrentModulePuIq0PuStart value of q-component current at injector terminal in pu (generator convention) (base SNom, UNom)
Types.PerUnitPF0Start value of powerfactor
Types.ActivePowerPuPInj0PuStart value of active power at injector terminal in pu (generator convention) (base SNom)
Types.ReactivePowerPuQInj0PuStart value of reactive power at injector terminal in pu (generator convention) (base SNom)
Types.VoltageModulePuUInj0PuStart value of voltage magnitude at injector terminal in pu (base UNom)
Electrical Control
BooleanPfFlagPower factor flag: Q control (0) or pf control(1)
BooleanPQFlagQ/P priority: Q priority (0) or P priority (1)
BooleanQFlagQ control flag: const. pf or Q ctrl (0) or voltage/Q (1)
BooleanVFlagVoltage control flag: voltage control (0) or Q ctrl (1)
Types.VoltageModulePuDbd1PuOvervoltage deadband for reactive current injection in pu (base UNom) (typical: -0.1..0)
Types.VoltageModulePuDbd2PuUndervoltage deadband for reactive current injection in pu (base UNom) (typical: 0..0.1)
Types.PerUnitDPMaxPuActive power upper rate limit in pu/s (base SNom) (typical: > 0.1, set to 99 to disable)
Types.PerUnitDPMinPuActive power lower rate limit in pu/s (base SNom) (typical: < -0.1, set to -99 to disable)
Types.CurrentModulePuIMaxPuMaximal apparent current magnitude in pu (base UNom, SNom) (typical: 1..2)
Types.PerUnitIqh1PuMaximum reactive current injection (typical: 1..1.1) in pu (base UNom, SNom)
Types.PerUnitIql1PuMinimum reactive current injection (typical: -1.1..-1) in pu (base UNom, SNom)
Types.PerUnitKqiIntegrator gain local reactive power PI controller
Types.PerUnitKqpProportional gain local reactive power PI controller
Types.PerUnitKqvK-Factor, reactive current injection gain (typical: 0..10)
Types.PerUnitKviIntegrator gain local voltage PI controller
Types.PerUnitKvpProportional gain local voltage PI controller
Types.ActivePowerPuPMaxPuActive power upper limit in pu (base SNom) (typical: 1)
Types.ActivePowerPuPMinPuActive power lower limit in pu (base SNom) (typical: 0)
Types.ReactivePowerPuQMaxPuReactive power upper limit, when vFlag == 1 in pu (base SNom)
Types.ReactivePowerPuQMinPuReactive power lower limit, when vFlag == 1 in pu (base SNom)
Types.TimetIqFilter time constant reactive current in s(typical: 0.01..0.02)
Types.TimetRvFilter time constant terminal voltage in s(typical: 0.01..0.02)
Types.TimetPFilter time constant active power in s (typical: 0.1..0.2)
Types.TimetPordFilter time constant inverter active power in s
Types.VoltageModulePuVDipPuLow voltage condition trigger voltage for FRT in pu (base UNom) (typical: 0..0.9)
Types.VoltageModulePuVMaxPuMaximum voltage at inverter terminal in pu (base UNom) (typical: 1.05..1.15)
Types.VoltageModulePuVMinPuMinimum voltage at inverter terminal in pu (base UNom) (typical: 0.85..0.95)
Types.VoltageModulePuVRef0PuReference voltage for reactive current injection in pu (base UNom) (typical: 0.95..1.05)
Types.VoltageModulePuVUpPuHigh voltage condition trigger voltage for FRT in pu (base UNom) (typical: 1.1..1.3)