| Plant Control |
| Boolean | FreqFlag | | Governor response disable (0) or enable (1) |
| Boolean | RefFlag | | Plant level reactive power (0) or voltage control (1) |
| Boolean | VCompFlag | | Reactive droop (0) or line drop compensation (1) if RefFlag true |
| Types.PerUnit | DbdPu | | Reactive power (RefFlag = 0) or voltage (RefFlag = 1) deadband in pu (base SNom or UNom) (typical: 0..0.1) |
| Types.PerUnit | DDn | | Down regulation droop (typical: 20..33.3) |
| Types.PerUnit | DUp | | Up regulation droop (typical: 0) |
| Types.PerUnit | EMaxPu | | Maximum Volt/VAR error in pu (base UNom or SNom) |
| Types.PerUnit | EMinPu | | Minimum Volt/VAR error in pu (base UNom or SNom) |
| Types.PerUnit | FDbd1Pu | | Overfrequency deadband for governor response in pu (base omegaNom) (typical: 0.004) |
| Types.PerUnit | FDbd2Pu | | Underfrequency deadband for governor response in pu (base omegaNom)^ (typical: 0.004) |
| Types.PerUnit | FEMaxPu | | Maximum frequency error in droop regulator in pu (base omegaNom) |
| Types.PerUnit | FEMinPu | | Minimum frequency error in droop regulator in pu (base omegaNom) |
| Types.PerUnit | Kc | | Reactive droop when VCompFlag = 0 |
| Types.PerUnit | Ki | | Volt/VAR regulator integral gain |
| Types.PerUnit | Kig | | Droop regulator integral gain |
| Types.PerUnit | Kp | | Volt/VAR regulator proportional gain |
| Types.PerUnit | Kpg | | Droop regulator proportional gain |
| Types.ActivePowerPu | PMaxPu | | Maximum plant level active power command in pu (base SNom) |
| Types.ActivePowerPu | PMinPu | | Minimum plant level active power command in pu (base SNom) |
| Types.ReactivePowerPu | QMaxPu | | Maximum plant level reactive power command in pu (base SNom) |
| Types.ReactivePowerPu | QMinPu | | Minimum plant level reactive power command in pu (base SNom) |
| Types.Time | tFilterPC | | Voltage and reactive power filter time constant in s (typical: 0.01..0.02) |
| Types.Time | tFt | | Plant controller Q output lead time constant in s |
| Types.Time | tFv | | Plant controller Q output lag time constant in s (typical: 0.15..5) |
| Types.Time | tLag | | Plant controller P output lag time constant in s(typical: 0.15..5) |
| Types.Time | tP | | Active power filter time constant in s (typical: 0.01..0.02) |
| Types.VoltageModulePu | VFrz | | Voltage for freezing Volt/VAR regulator integrator (typical: 0..0.9) |