recordParamsREEC

Common REEC parameters

Parameters

TypeNameDefaultDescription
Types.ApparentPowerModuleSNomNominal apparent power in MVA
Types.CurrentModulePuId0PuStart value of d-component current at injector terminal in pu (generator convention) (base SNom, UNom)
Types.CurrentModulePuIq0PuStart value of q-component current at injector terminal in pu (generator convention) (base SNom, UNom)
Types.PerUnitPF0Start value of power factor
Types.ActivePowerPuPConv0PuStart value of active power at converter terminal in pu (generator convention) (base SNom)
Types.ReactivePowerPuQConv0PuStart value of reactive power at converter terminal in pu (generator convention) (base SNom)
Types.VoltageModulePuUInj0PuStart value of voltage magnitude at injector terminal in pu (base UNom)
Types.ComplexPerUnits0PuStart value of complex apparent power at terminal in pu (base SnRef) (receptor convention)
Types.ComplexVoltagePuu0PuStart value of complex voltage at terminal in pu (base UNom)
Types.VoltageModulePuUConv0PuStart value of voltage module at converter terminal in pu (base UNom)
Types.ComplexPerUnituConv0PuStart value of complex voltage at converter terminal in pu (base UNom)
Electrical Control › REEC
BooleanPfFlagPower factor flag: Q control (0) or pf control(1)
BooleanPQFlagQ/P priority: Q priority (0) or P priority (1)
BooleanQFlagQ control flag: const. pf or Q ctrl (0) or voltage/Q (1)
BooleanVFlagVoltage control flag: voltage control (0) or Q ctrl (1)
Types.VoltageModulePuDbd1PuOvervoltage deadband for reactive current injection in pu (base UNom) (typical: -0.1..0)
Types.VoltageModulePuDbd2PuUndervoltage deadband for reactive current injection in pu (base UNom) (typical: 0..0.1)
Types.PerUnitDPMaxPuActive power upper rate limit in pu/s (base SNom) (typical: > 0.1, set to 99 to disable)
Types.PerUnitDPMinPuActive power lower rate limit in pu/s (base SNom) (typical: < -0.1, set to -99 to disable)
Types.CurrentModulePuIMaxPuMaximal apparent current magnitude in pu (base UNom, SNom) (typical: 1..2)
Types.PerUnitIqh1PuMaximum reactive current injection (typical: 1..1.1) in pu (base UNom, SNom)
Types.PerUnitIql1PuMinimum reactive current injection (typical: -1.1..-1) in pu (base UNom, SNom)
Types.PerUnitKqiIntegrator gain local reactive power PI controller
Types.PerUnitKqpProportional gain local reactive power PI controller
Types.PerUnitKqvK-Factor, reactive current injection gain (typical: 0..10)
Types.PerUnitKviIntegrator gain local voltage PI controller
Types.PerUnitKvpProportional gain local voltage PI controller
Types.ActivePowerPuPMaxREECPuActive power upper limit in REEC in pu (base SNom) (typical: 1)
Types.ActivePowerPuPMinREECPuActive power lower limit in REEC in pu (base SNom) (typical: 0)
Types.ReactivePowerPuQMaxREECPuReactive power upper limit, when vFlag == 1 in REEC in pu (base SNom)
Types.ReactivePowerPuQMinREECPuReactive power lower limit, when vFlag == 1 in REEC in pu (base SNom)
Types.TimetIqFilter time constant reactive current in s(typical: 0.01..0.02)
Types.TimetRvFilter time constant terminal voltage in s(typical: 0.01..0.02)
Types.TimetpREECActive power filter time constant in REEC in s (typical: 0.1..0.2)
Types.TimetPordFilter time constant inverter active power in s
Types.VoltageModulePuVDipPuLow voltage condition trigger voltage for FRT in pu (base UNom) (typical: 0..0.9)
Types.VoltageModulePuVMaxPuMaximum voltage at inverter terminal in pu (base UNom) (typical: 1.05..1.15)
Types.VoltageModulePuVMinPuMinimum voltage at inverter terminal in pu (base UNom) (typical: 0.85..0.95)
Types.VoltageModulePuVRef0PuReference voltage for reactive current injection in pu (base UNom) (typical: 0.95..1.05)
Types.VoltageModulePuVUpPuHigh voltage condition trigger voltage for FRT in pu (base UNom) (typical: 1.1..1.3)