recordParamsREECa

REEC type A parameters

Parameters

TypeNameDefaultDescription
Types.AngularVelocityPuomegaRefWTGQ0PuStart value of reference angular frequency of torque control in pu (base omegaNom)
Electrical Control › REECa
Types.PerUnitVDLIp11
Types.PerUnitVDLIp12
Types.PerUnitVDLIp21
Types.PerUnitVDLIp22
Types.PerUnitVDLIp31
Types.PerUnitVDLIp32
Types.PerUnitVDLIp41
Types.PerUnitVDLIp42
Types.PerUnitVDLIq11
Types.PerUnitVDLIq12
Types.PerUnitVDLIq21
Types.PerUnitVDLIq22
Types.PerUnitVDLIq31
Types.PerUnitVDLIq32
Types.PerUnitVDLIq41
Types.PerUnitVDLIq42
Types.PerUnit[:,:]VDLIpPoints[VDLIp11, VDLIp12; VDLIp21, VDLIp22; VDLIp31, VDLIp32; VDLIp41, VDLIp42]Pair of points for voltage-dependent active current limitation piecewise linear curve [u1,y1; u2,y2;...]
Types.PerUnit[:,:]VDLIqPoints[VDLIq11, VDLIq12; VDLIq21, VDLIq22; VDLIq31, VDLIq32; VDLIq41, VDLIq42]Pair of points for voltage-dependent reactive current limitation piecewise linear curve [u1,y1; u2,y2;...]
Types.TimetHoldIpMaxTime delay for which the active current limit (ipMaxPu) is held after voltage dip in s
Types.TimetHoldIqAbsolute value of tHoldIq defines seconds to hold current injection after voltage dip ended. tHoldIq > 0 for constant, 0 for no injection after voltage dip, tHoldIq < 0 for voltage-dependent injection (typical: -1 .. 1 s)
Types.PerUnitIqFrzPuConstant reactive current injection value in pu (base UNom, SNom) (typical: -0.1 .. 0.1 pu)
BooleanPFlagPower reference flag: const. Pref (0) or consider generator speed (1)
Types.VoltageModulePuVRef1PuUser-defined reference/bias on the inner-loop voltage control in pu (base UNom) (typical: 0 pu)