modelElectronicLoad

Constant power load with disconnection and reconnections depending on the voltage

Extends from BaseClasses.BaseLoad (Base model for loads), AdditionalIcons.Load.

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
Constants.stateState0 (from SwitchOffLoad)Constants.state.ClosedStart value of connection state
Types.ComplexVoltagePuu0Pu (from BaseLoad)Start value of complex voltage at load terminal in pu (base UNom)
Types.ComplexApparentPowerPus0Pu (from BaseLoad)Start value of apparent power at load terminal in pu (base SnRef) (receptor convention)
Types.ComplexCurrentPui0Pu (from BaseLoad)Start value of complex current at load terminal in pu (base UNom, SnRef) (receptor convention)
Types.VoltageModulePuUd1PuVoltage at which the load starts to disconnect in pu (base UNom)
Types.VoltageModulePuUd2PuVoltage at which the load is completely disconnected in pu (base UNom)
RealrecoveringShareShare of the load that recovers from low voltage trip
Types.TimetFilter1e-2Time constant for estimation of UMinPu in s

Connectors

TypeNameDefaultDescription
Dynawo.Connectors.BPinswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Dynawo.Connectors.BPinswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Dynawo.Connectors.BPinswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Dynawo.Connectors.BPinrunning (from SwitchOffLogic)Indicates if the component is running or not
Dynawo.Connectors.ACPowerterminal (from BaseLoad)Connector used to connect the load to the grid
Modelica.Blocks.Interfaces.RealInputPRefPu (from BaseLoad)Active power request
Modelica.Blocks.Interfaces.RealInputQRefPu (from BaseLoad)Reactive power request
Modelica.Blocks.Interfaces.RealInputdeltaP (from BaseLoad)Delta to apply on PRef in %
Modelica.Blocks.Interfaces.RealInputdeltaQ (from BaseLoad)Delta to apply on QRef in %
Dynawo.Connectors.ImPinUPu (from BaseLoad)Voltage amplitude at load terminal in pu (base UNom)

Components

TypeNameDefaultDescription
Constants.statestate (from SwitchOffLoad)Load connection state
Types.ActivePowerPuPPu (from BaseLoad)Active power at load terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQPu (from BaseLoad)Reactive power at load terminal in pu (base SnRef) (receptor convention)
Types.ComplexApparentPowerPuSPu (from BaseLoad)Apparent power at load terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuUMinPuMinimum voltage during the simulation (with lower bound at Ud2Pu) in pu (base UNom)
RealconnectedShareShare of the load that is currently connected