modelGeneratorPTanPhi

Generator PV when linked to reactive power control loop

Extends from Dynawo.AdditionalIcons.Machine, Dynawo.Electrical.Machines.BaseClasses.BaseGeneratorSimplified (Base model for simplified generator models).

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
Constants.stateState0 (from SwitchOffGenerator)Constants.state.ClosedStart value of connection state
Types.ActivePowerPuPGen0Pu (from BaseGeneratorSimplified)Start value of active power at terminal in pu (base SnRef) (generator convention)
Types.ReactivePowerPuQGen0Pu (from BaseGeneratorSimplified)Start value of reactive power at terminal in pu (base SnRef) (generator convention)
Types.VoltageModulePuU0Pu (from BaseGeneratorSimplified)Start value of voltage amplitude at terminal in pu (base UNom)
Types.ComplexVoltagePuu0Pu (from BaseGeneratorSimplified)Start value of complex voltage at terminal in pu (base UNom)
Types.ComplexCurrentPui0Pu (from BaseGeneratorSimplified)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
Types.PerUnitAlphaPuPNomFrequency sensitivity in pu (base PNom, OmegaNom)
Types.ActivePowerPMaxMaximum active power in MW
Types.ActivePowerPMinMinimum active power in MW
Types.ActivePowerPNomNominal active power in MW
Types.ReactivePowerQMaxMaximum reactive power in Mvar
Types.ReactivePowerQMinMinimum reactive power in Mvar
RealTanPhiRefif PGen0Pu <> 0 then QGen0Pu/PGen0Pu else 0Start value of tan(Phi) regulation set point at terminal
Types.ApparentPowerModuleSNomApparent nominal power in MVA
Types.ReactivePowerPuQMaxPuQMax/SystemBase.SnRefMaximum reactive power in pu (base SnRef)
Types.ReactivePowerPuQMinPuQMin/SystemBase.SnRefMinimum reactive power in pu (base SnRef)
Types.ActivePowerPuPMinPuPMin/SystemBase.SnRefMinimum active power in pu (base SnRef)
Types.ActivePowerPuPMaxPuPMax/SystemBase.SnRefMaximum active power in pu (base SnRef)
Types.PerUnitAlphaPuAlphaPuPNom*PNom/SystemBase.SnRefFrequency sensitivity in pu (base SnRef, OmegaNom)

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Modelica.Blocks.Interfaces.BooleanOutputrunning (from SwitchOffLogic)Indicates if the component is running or not
Dynawo.Connectors.ACPowerterminal (from BaseGeneratorSimplified)Connector used to connect the synchronous generator to the grid
Dynawo.Connectors.ReactivePowerPuOutputQGenPu (from BaseGeneratorSimplified)Reactive power at terminal in pu (base SnRef) (generator convention)
Dynawo.Connectors.VoltageModulePuOutputUPu (from BaseGeneratorSimplified)Voltage amplitude at terminal in pu (base UNom)
Modelica.Blocks.Interfaces.RealInputPVariationPercentage variation of active power reference
Modelica.Blocks.Interfaces.RealInputdeltaPRefPuAdditional active power reference in pu (base PNom)
Modelica.Blocks.Interfaces.RealInputomegaRefPuNetwork angular reference frequency in pu (base OmegaNom)

Components

TypeNameDefaultDescription
Constants.statestate (from SwitchOffGenerator)Generator connection state
RealgenState (from SwitchOffGenerator)Generator continuous connection state
Modelica.Blocks.Math.IntegerToRealconverter (from SwitchOffGenerator)Converter for generator state
Types.ActivePowerPGen (from BaseGeneratorSimplified)Active power at terminal in MW (generator convention)
Types.ActivePowerPuPGenPu (from BaseGeneratorSimplified)Active power at terminal in pu (base SnRef) (generator convention)
Types.ComplexApparentPowerPuSGenPu (from BaseGeneratorSimplified)Complex apparent power at terminal in pu (base SnRef) (generator convention)

Contents

NameDescription
QStatus
PStatus