modelGeneratorPVTfoDiagramPQ_INIT

Initialisation model for generator PV based on SignalN for the frequency handling, with a transformer, a voltage regulation at stator and with an N points PQ diagram. The voltage module reference at stator is calculated using the voltage module reference at terminal.

Extends from BaseClasses_INIT.BaseGeneratorSignalNPQDiagram_INIT (Base initialization model for SignalN generator models with PQ diagram), AdditionalIcons.Init.

Parameters

TypeNameDefaultDescription
Types.ComplexCurrentPuiStart0Pu (from BaseGeneratorParameters_INIT)Complex(0, 0)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
Types.ActivePowerPuP0Pu (from BaseGeneratorParameters_INIT)Start value of active power at terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0Pu (from BaseGeneratorParameters_INIT)Start value of reactive power at terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from BaseGeneratorParameters_INIT)Start value of voltage amplitude at terminal in pu (base UNom)
Types.AngleUPhase0 (from BaseGeneratorParameters_INIT)Start value of voltage angle at terminal in rad
Types.ActivePowerPuPMax (from BaseGeneratorSignalNPQDiagram_INIT)Maximum active power in MW
Types.ActivePowerPuPMin (from BaseGeneratorSignalNPQDiagram_INIT)Minimum active power in MW
Types.ReactivePowerPuQMax0 (from BaseGeneratorSignalNPQDiagram_INIT)Start value of maximum reactive power in Mvar
Types.ReactivePowerPuQMin0 (from BaseGeneratorSignalNPQDiagram_INIT)Start value of minimum reactive power in Mvar
Types.ReactivePowerQNomAltNominal reactive power of the generator in Mvar
Types.ApparentPowerModuleSNomNominal apparent power of the generator in MVA
Types.PerUnitXTfoPuReactance of the generator transformer in pu (base UNom, SNom)
Types.VoltageModulePuURef0PuStart value of the voltage regulation set point at terminal in pu (base UNom)

Components

TypeNameDefaultDescription
Types.ActivePowerPuPGen0Pu (from BaseGeneratorParameters_INIT)Start value of active power at terminal in pu (base SnRef) (generator convention)
Types.ReactivePowerPuQGen0Pu (from BaseGeneratorParameters_INIT)Start value of reactive power at terminal in pu (base SnRef) (generator convention)
Types.ComplexVoltagePuu0Pu (from BaseGeneratorParameters_INIT)Start value of complex voltage at terminal in pu (base UNom)
Types.ComplexApparentPowerPus0Pu (from BaseGeneratorParameters_INIT)Start value of complex apparent power at terminal in pu (base SnRef) (receptor convention)
Types.ComplexCurrentPui0Pu (from BaseGeneratorParameters_INIT)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
BooleanlimUQDown0 (from BaseGeneratorSignalNPQDiagram_INIT)Whether the minimum reactive power limits are reached or not (from generator voltage regulator), start value
BooleanlimUQUp0 (from BaseGeneratorSignalNPQDiagram_INIT)Whether the maximum reactive power limits are reached or not (from generator voltage regulator), start value
Types.ActivePowerPuPMaxPu (from BaseGeneratorSignalNPQDiagram_INIT)Maximum active power in pu (base SnRef)
Types.ActivePowerPuPMinPu (from BaseGeneratorSignalNPQDiagram_INIT)Minimum active power in pu (base SnRef)
Types.ReactivePowerPuQMax0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of maximum reactive power in pu (base SnRef)
Types.ReactivePowerPuQMin0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of minimum reactive power in pu (base SnRef)
QStatusqStatus0 (from BaseGeneratorSignalNPQDiagram_INIT)Start voltage regulation status: standard, absorptionMax or generationMax
Types.ComplexCurrentPuiStator0PuStart value of complex current at stator in pu (base UNom, SNom) (generator convention)
Types.ReactivePowerPuQStator0PuStart value of stator reactive power in pu (base QNomAlt) (generator convention)
Types.ComplexApparentPowerPusStator0PuStart value of complex apparent power at stator in pu (base UNom, SNom) (generator convention)
Types.ComplexVoltagePuuStator0PuStart value of complex voltage at stator in pu (base UNom)
Types.VoltageModulePuUStator0PuStart value of voltage module at stator in pu (base UNom)
Types.ComplexVoltagePuuStatorRef0PuStart value of complex voltage regulation set point at stator in pu (base UNom)
Types.VoltageModulePuUStatorRef0PuStart value of voltage regulation set point at stator in pu (base UNom)