modelShuntB

Shunt element with constant susceptance, reactive power depends on voltage

Extends from AdditionalIcons.Shunt, Dynawo.Electrical.Controls.Basics.SwitchOff.SwitchOffShunt (Switch-off model for a shunt).

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
Constants.stateState0 (from SwitchOffShunt)Constants.state.ClosedStart value of connection state
Types.PerUnitBPuSusceptance in pu (base SnRef), negative values for capacitive consumption (over-excited), positive values for inductive consumption (under-excited)
Types.ComplexVoltagePuu0PuStart value of complex voltage at shunt terminal in pu (base UNom)
Types.ComplexApparentPowerPus0PuStart value of apparent power at shunt terminal in pu (base SnRef, receptor convention)
Types.ComplexCurrentPui0PuStart value of complex current at shunt terminal in pu (base UNom, SnRef, receptor convention)

Connectors

TypeNameDefaultDescription
Dynawo.Connectors.BPinswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Dynawo.Connectors.BPinswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Dynawo.Connectors.BPinswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Dynawo.Connectors.BPinrunning (from SwitchOffLogic)Indicates if the component is running or not
Dynawo.Connectors.ACPowerterminalConnector used to connect the shunt to the grid

Components

TypeNameDefaultDescription
Constants.statestate (from SwitchOffShunt)Shunt connection state
Types.VoltageModulePuUPuVoltage amplitude at shunt terminal in pu (base UNom)
Types.ActivePowerPuPPuActive power at shunt terminal in pu (base SnRef, receptor convention)
Types.ReactivePowerPuQPuReactive power at shunt terminal in pu (base SnRef, receptor convention)
Types.ComplexApparentPowerPuSPuApparent power at shunt terminal in pu (base SnRef, receptor convention)