modelTransformerVariableTapControlled

Extends from AdditionalIcons.Transformer, Dynawo.Electrical.Controls.Basics.SwitchOff.SwitchOffTransformer (Switch-off signal for a transformer).

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
Constants.stateState0 (from SwitchOffTransformer)Constants.state.ClosedStart value of connection state
BooleanincreaseTapToIncreaseValueWhether increasing the tap will increase the monitored value
Booleanregulating0Whether the tap-changer/phase-shifter is initially regulating
Statestate0Initial state
IntegertapMinMinimum tap
IntegertapMaxMaximum tap
IntegerTap0Initial tap
Types.Timet1stTime lag before changing the first tap in s
Types.TimetNextTime lag before changing subsequent taps in s
Types.VoltageModuleU0Initial voltage
Types.VoltageModuleUDeadBandVoltage dead-band
Types.VoltageModuleUTargetVoltage set-point
Types.VoltageModuleUNom1Nominal voltage in kV
Types.ApparentPowerModuleSNomNominal apparent power in MVA
Types.PercentRResistance in % (base U2Nom, SNom)
Types.PercentXReactance in % (base U2Nom, SNom)
Types.PercentGConductance in % (base U2Nom, SNom)
Types.PercentBSusceptance in % (base U2Nom, SNom)
Types.PerUnitrTfoMinPuMinimum transformation ratio in pu: U2/U1 in no load conditions
Types.PerUnitrTfoMaxPuMaximum transformation ratio in pu: U2/U1 in no load conditions
IntegerNbTapNumber of taps
Types.ComplexCurrentPui20PuStart value of complex current at terminal 2 in pu (base U2Nom, SnRef) (receptor convention)
Types.ComplexCurrentPui10PuStart value of complex current at terminal 1 in pu (base U1Nom, SnRef) (receptor convention)
Types.ComplexVoltagePuu10PuStart value of complex voltage at terminal 1 in pu (base U1Nom)
Types.ComplexVoltagePuu20PuStart value of complex voltage at terminal 2 in pu (base U2Nom)
Types.PerUnitrTfo0PuStart value of transformer ratio
Types.ActivePowerPuP10PuStart value of active power at terminal 1 in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ10PuStart value of reactive power at terminal 1 in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU10PuStart value of voltage amplitude at terminal 1 in pu (base U1Nom)
Types.VoltageModulePuU20PuStart value of voltage amplitude at terminal 2 in pu (base U2Nom)

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Modelica.Blocks.Interfaces.BooleanOutputrunning (from SwitchOffLogic)Indicates if the component is running or not
Modelica.Blocks.Interfaces.RealOutputP1PuActive power on side 1
Modelica.Blocks.Interfaces.RealOutputQ1PuReactive power on side 1
Dynawo.Connectors.ACPowerterminal2
Dynawo.Connectors.ACPowerterminal1

Components

TypeNameDefaultDescription
Constants.statestate (from SwitchOffTransformer)Transformer connection state
Dynawo.Electrical.Transformers.TransformersVariableTap.TransformerVariableTaptransformerVariableTap
Dynawo.Electrical.Controls.Transformers.TapChangertapChanger
BooleanlockedWhether the tap-changer is locked

Contents

NameDescription
State