modelSheetI10
Extends from Icons.Example (Icon for runnable examples), Examples.GridCodeSimulations.BaseSheetSimulations.BaseSheetI10, Examples.GridCodeSimulations.BaseUnitModel.
Information
Test Case: Islanding
1. Objective
This test evaluates the behavior of a production unit operating in islanded conditions following a sudden load variation. It verifies frequency stability, voltage stability, and protection robustness.
2. Network Configuration
The test is performed on an isolated network composed of:
- One production unit
- One synchronous compensator
- One load
3. Initial Operating Conditions
3.1 Production Unit
-
Active power at PCC:
-
Reactive power at PCC:
-
Voltage at PCC:
3.2 Synchronous Compensator
- Model: classical model with internal voltage source behind reactance
-
Rated apparent power:
-
Reactance:
- Inertia constant:
Where:
Alternative formulation:
3.3 Load
-
Active power consumption:
-
Reactive power:
-
Model:
- Constant power load (PQ model)
- No dependency on voltage or frequency
4. Disturbance Description
At , the following step is applied:
-
Active power increase:
-
Reactive power variation:
5. Expected Behaviour / Compliance Criteria
The system is considered compliant if the following conditions are met:
5.1 Protection
- The production unit must not trip due to internal protections
5.2 Stability
- The system must reach a stable operating point
-
No sustained oscillations in:
- Frequency
- Voltage
5.3 Frequency Limits
-
Frequency must remain within:
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Types.ApparentPowerModule | SNom (from BaseParameters) | 35 | Nominal apparent power in MVA |
| Types.PerUnit | XaPu (from BaseParameters) | 0.05*Electrical.SystemBase.SnRef/SNom | Reactance a of the DTR in pu (base SnRef, UNom) |
| Types.PerUnit | XbPu (from BaseParameters) | 0.3*Electrical.SystemBase.SnRef/SNom | Reactance b of the DTR in pu (base SnRef, UNom) |
| Types.ActivePowerPu | P0Pu (from BaseParameters) | -1*SNom/Electrical.SystemBase.SnRef | Start value of active power at regulated bus in pu (receptor convention) (base SnRef) |
| Types.ReactivePowerPu | Q0Pu (from BaseParameters) | 0*SNom/Electrical.SystemBase.SnRef | Start value of reactive power at regulated bus in pu (receptor convention) (base SnRef) |
| Types.VoltageModulePu | U0Pu (from BaseParameters) | 1 | Start value of voltage magnitude at regulated bus in pu (base UNom) |
| Types.VoltageModulePu | UInfPu (from BaseParameters) | sqrt((P0Pu*XccPu)^2 + (Q0Pu*XccPu + U0Pu^2)^2)/U0Pu | Value of voltage magnitude at infinite in pu (base UNom) |
| Types.Angle | UPhase0 (from BaseParameters) | Modelica.Math.atan2(-P0Pu*XccPu, Q0Pu*XccPu + U0Pu^2) | Start value of voltage phase angle at regulated bus in rad |
| Types.PerUnit | XccPu (from BaseParameters) | Reactance of equivalent branch connection to the grid in pu (base SnRef, UNom) |