.Dynawo.Examples.Nordic.Components.TransformerWithControl.TransformerWithControl

Model of transformer with variable tap, for the Nordic 32 test system

Information

The controlled tfo frame represents the regulated transformer of the Nordic 32 test system.
It consists of a variable tap transformer and an on-load tap changer with 33 positions, keeping the transformer ratios in the interval [0.88, 1.20] and the distribution voltage in the deadband [0.99, 1.01].
The implementation uses a transformer preset, which automatically sets the parameters of all elements to those of the corresponding chosen transformer.
To add another configuration, append a new line to "tfoParamValues" in TransformerParameters and append a fitting name in the "tfoPreset" enumeration.