This test case simulates a load variation.
The SVarC is initially in the standby mode.
A large reactive load variation of Q=300 Mvar is realised at t = 1 s.
The SVarC switches to running mode after the load variation and regulates with the reference URefDown.
The provided current reaches its limitation and the current limitor is activated in order to bring the current back to an acceptable value.
Generated at 2024-12-04T19:25:49Z
by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos