.Greenhouses.Flows.HeatAndVapourTransfer.VentilationRates.NaturalVentilationRate_2

Air exchange rate from the greenhouse air to the outside air function of wind and temperature by Boulard and Baille (1995)

Information

The natural ventilation rate due to roof ventilation is described by Boulard and Baille (1995):

f_vent = U_Roof*A_Roof*C_d/(2*A_Flr)*sqrt(g*h_vent/2 * (T_Air-T_Out)/(T_mean+273.15)+C_w*u_wind^2)

where

Since it is considered that the greenhouse does not have side vents, the whole ventilation rate is through the roof vents.

The discharge coefficients C_w and C_d depend on the use of an external shading screen. However, it is considered that in the studied greenhouse there is no external shading screen.