.IBPSA.Fluid.Geothermal.Borefields.BaseClasses.HeatTransfer.LoadAggregation.temporalSuperposition

Information

Performs the temporal superposition operation to obtain the temperature change at the borehole wall at the current time step, which is the scalar product of the aggregated load vector and the kappa step response vector. To avoid unnecessary calculations, the current aggregation cell in the simulation is used to truncate the values from the vectors that are not required.

Interface

function temporalSuperposition
  extends Modelica.Icons.Function;
  input Integer i "Number of aggregation cells";
  input Modelica.SIunits.HeatFlowRate QAgg_flow[i] "Vector of aggregated loads";
  input Modelica.SIunits.ThermalResistance kappa[i] "Weighting factors for each aggregation cell";
  input Integer curCel "Current occupied aggregation cell";
  output Modelica.SIunits.TemperatureDifference deltaTb "Delta T at wall";
end temporalSuperposition;

Revisions


Generated at 2024-12-25T19:25:50Z by OpenModelicaOpenModelica 1.24.3 using GenerateDoc.mos