Description
This block computes the set point temperatures for the supply and return temperature of a heating system. The set point for the room air temperature can either be specified by a parameter, or it can be an input to the model. The latter allows to use this model with systems that have night set back.
The parameter dTOutHeaBal can be used to shift the
heating curve to account for the fact that solar heat gains and
heat gains from equipment and people make up for some of the
transmission losses. For example, in energy efficient houses, the
heating may not be switched on above 12 degree Celsius, even if a
room temperature of 20 degree is required. In such a situation, set
dTOutHeaBal=20-12=8 Kelvin to shift the heating
curve.
The outdoor temperature is filtered with a first order or moving average filter (replaceable component). The time constant of this filter can be set.
If desired (minSup=true), a minimum supply temperature can be set for the heating curve output.
No validation performed.
No specific example foreseen for the heating curve, see the heating system examples.