This block computes the set point temperatures for the supply and return water temperature. The set point for the room air temperature can either be specified by a parameter, or it can be an input to the model. The latter allows to use this model with systems that have night set back.
If used to reset the temperature in a heating system, the
parameter dTOutHeaBal can be used to shift the heating
curve to take into account that heat gains from solar, equipment
and people make up for some of the transmission losses. For
example, in energy efficient houses, the heating may not be
switched on if the outside air temperature is greater than
12°C, even if a room temperature of 20°C is required.
In such a situation, set dTOutHeaBal=20-12=8 Kelvin to
shift the heating curve.
HideResult.HotWaterTemperatureReset to
SupplyReturnTemperatureReset.Evaluate=true.TRoo_nominal. See ticket #74.